ملخص المحتوى في الصفحة رقم 1
G
H
I N
T
G
N
WI
Y
T
L
I
P
D
CE
O
M
ON
S C
C
RT
-
I
R
F
I A
E
A R
I
I
R
I
Q
CA
A
A
T
U
S T
I
O
I
A
O
036-21004-002 Rev. B (0602)
DESCRIPTION
The 14 SEER Series condensing unit is the outdoor part of a
TECHNICAL
TECHNICAL
versatile system of air conditioning. It is designed to be cus-
tom-matched with one of UPGs complete line of evaporator
sections, with each serving a specific function. Matching Air
GUIDE
GUIDE
Handlers are available for upflow, downflow, or horizontal
applications to provid
ملخص المحتوى في الصفحة رقم 2
036-21004-002 Rev. B (0602) Physical and Electrical Data MODEL FRCS0241BD FRCS0301BD FRCS0361CD FRCS0421CE FRCS0481CE FRCS0601BF Unit Supply Voltage 208 / 230 - 1 60 1 187 to 252 Normal Voltage Range Minimum Circuit Ampacity 12.1 14.9 18.1 17.8 20.6 31.8 2 20 20 25 30 35 50 Max Overcurrent Device Amps 3 C C C B Inertia Inertia Compressor Type Scroll Scroll Scroll Scroll Rated Load 9.3 10.9 13.5 13.2 15.5 24.3 Compressor Amps Locked Rotor 57 64 73 95 109 150 Crankcase Heater No No No No No No F
ملخص المحتوى في الصفحة رقم 3
036-21004-002 Rev. B (0602) COOLING CAPACITY - With Air Handler Coils AIR HANDLER COOLING 1 COIL 2 UNIT MODEL NET MBH SEER RATED SEER ELECTRIC MODEL W MODEL EER 3 CFM W/O TXV HEAT KW + TXV TOTAL SENS. 1 PH 14 SEER AC WITH N-AH / G2FD FRCS0241BD N1AHB0806 2,5,8,10 17 G2FD036S17 800 25.2 18.1 - 14.00 12.35 FRCS0301BD N1AHB1206 5,8,10,15,19 17 G2FD036S17 1000 28.8 20.7 - 13.10 11.80 N1AHB1206 5,8,10,15,19 17 G2FD036S17 1200 34.0 24.5 - 13.35 11.80 N1AHB1206 5,8,10,15,19 17 G2FD046S17 1200 35.0 25
ملخص المحتوى في الصفحة رقم 4
036-21004-002 Rev. B (0602) COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils FURNACE** COOLING COIL 1 NET MBH UNIT MODEL CFM RANGE RATED SEER + TXV SEER + TXV W MODEL EER (MIN.-MAX.) CFM W/O TDR TOTAL SENS. + TDR* 14 G1FA036S14 800 25.0 18.0 13.85 - 12.30 17,21 G1FA036S17,21 800 24.8 17.9 13.85 - 12.20 - G1HD036 800 25.0 18.1 14.00 - 12.35 17 G1NA036S17L 800 24.0 16.6 13.50 - 12.00 21 G1NA048S21D 800 24.0 16.6 13.50 - 12.00 700 14 G1UA036S14 800 25.0 18.0 13.85 - 12.30 FRCS02
ملخص المحتوى في الصفحة رقم 5
036-21004-002 Rev. B (0602) COOLING CAPACITY - Upflow, Downflow, & Horizontal Furnaces and Coils (Continued) FURNACE** COOLING COIL 1 UNIT MODEL NET MBH CFM RANGE RATED SEER + TXV SEER + TXV MODEL W EER (MIN.-MAX.) CFM TOTAL SENS. W/O TDR + TDR* 21,24 G1FA060S21,24 1900 53.5 37.1 - 13.25 12.00 24 G2FD060S24 1900 53.5 37.1 - 13.25 12.00 1650 24 G2FD061H24 2050 54.5 39.1 - 13.25 12.10 FRCS0601BF 2150 - G1HD060 1900 52.5 36.0 - 13.00 11.75 24 G1NA060S24T 1900 53.0 35.9 - 13.00 11.90 21,24 G1UA060S
ملخص المحتوى في الصفحة رقم 6
036-21004-002 Rev. B (0602) COOLING PERFORMANCE AIR TEMP ON CONDENSER AIR TEMP ON CONDENSER SUCT. T/P SUCT. T/P @ COMPR. @ COMPR. MODEL 75×F 95×F 115×F MODEL 75×F 95×F 115×F TEMP. PSIG MBH KW MBH KW MBH KW TEMP. PSIG MBH KW MBH KW MBH KW 35 61.5 22.9 1.42 19.4 1.63 15.9 1.82 35 61.5 36.1 2.31 31.7 2.94 27.5 3.81 40 68.5 25.3 1.45 21.6 1.67 18.0 1.90 40 68.5 39.3 2.33 34.6 2.95 30.1 3.81 FRCS0241BD FRCS0421CE 45 76.0 28.0 1.47 24.0 1.72 20.1 1.97 45 76.0 42.6 2.35 37.7 2.97 32.9 3.83 50 84.0 30.7
ملخص المحتوى في الصفحة رقم 7
036-21004-002 Rev. B (0602) TYPICAL INSTALLATION MINIMUM 18” SERVICE ACCESS THERMOSTAT TO FURNACE OR CLEARANCE ON ONE SIDE 60” OVERHEAD AIR HANDLER CLEARANCE WEATHERPROOF TERMINAL BLOCK DISCONNECT SWITCH NEC CLASS 1 WIRING NEC CLASS 2 WIRING 10” CLEARANCE TO INDOOR COIL COILAREA SEAL OPENING(S) WITH NOTE: ALL OUTDOOR WIRING PERMAGUM OR EQUIVALENT MUST BE WEATHERPROOF. CONTROLACCESS PANEL TYPICAL FIELD WIRING ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER
ملخص المحتوى في الصفحة رقم 8
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0241BD INDOOR COIL MODEL NO. F2RP/F2FP036 ID CFM 1100 1250 1350 CONDENSER ENTERING AIR ID DB 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 30.2 27.8 25.4 23.3 30.6 28.2 25.8 23.9 30.7 28.3 26.1 24.3 75 S.C. 17.7 17.8 17.9 17.9 19.1 19.0 19.2 18.9 19.8 19.7 19.8 19.1 K.W 1.75 1.74 1.721.701.811.791.781.771.831.821.811.79 T.C. 28.5 26.2 23.9 22.1 28.8 26.5 24.3 22.6 2
ملخص المحتوى في الصفحة رقم 9
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0301BD INDOOR COIL MODEL NO. G1FA048S21, 24 ID CFM 800 1000 1200 CONDENSER ENTERING AIR ID DB 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 35.9 32.8 30.2 27.0 36.6 33.5 30.9 27.7 36.9 33.8 31.4 28.1 75 S.C. 21.2 21.2 20.4 21.4 22.8 22.9 22.0 23.1 23.9 23.9 23.1 24.2 K.W 1.68 1.701.711.701.681.691.701.701.671.691.70 1.70 T.C. 34.1 31.1 28.6 25.6 34.7 31.7 29.3 26.2
ملخص المحتوى في الصفحة رقم 10
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0361CD INDOOR COIL MODEL NO. G1FA048S21, 24 ID CFM 1000 1200 1400 CONDENSER ENTERING AIR ID DB 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB 72 67 57 72 67 57 72 67 57 T.C. 40.0 36.9 34.3 41.3 38.1 35.7 42.0 38.9 36.7 75 S.C. 25.4 24.4 23.4 27.6 26.3 25.5 29.6 27.9 27.2 K.W 1.98 1.96 1.94 1.99 1.97 1.95 2.00 1.98 1.96 T.C. 38.6 35.6 32.7 39.6 36.6 34.0 40.2 37.3 34.9 85 S.C. 24.8 23.8 22.8 27.0 25.8 24.9 29.1 27.6
ملخص المحتوى في الصفحة رقم 11
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0421CE INDOOR COIL MODEL NO. G1FA060S21,24 ID CFM 1300 1450 1550 CONDENSER ENTERING AIR ID DB 85 80 75 70 85 80 75 70 85 80 75 70 TEMPERATURE ID WB 72 67 62 57 72 67 62 57 72 67 62 57 T.C. 47.3 43.8 40.3 37.2 47.7 44.3 40.9 37.7 48.0 44.5 41.2 38.0 75 S.C. 28.3 28.5 28.9 29.2 29.8 30.0 30.6 30.7 30.8 31.0 31.6 31.7 K.W 2.88 2.842.802.772.952.902.872.843.002.952.91 2.88 T.C. 44.6 41.3 38.1 35.1 45.0 41.8 38.6 35.
ملخص المحتوى في الصفحة رقم 12
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0481CE INDOOR COIL MODEL NO. G1FA060S21,24 ID CFM 1400 1600 1800 CONDENSER ENTERING AIR ID DB 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB 72 67 57 72 67 57 72 67 57 T.C. 53.3 49.5 45.5 54.3 50.2 46.4 55.2 51.0 47.3 75 S.C. 33.4 32.6 31.1 35.9 35.0 33.0 38.3 37.4 34.9 K.W 2.76 2.72 2.69 2.77 2.74 2.70 2.77 2.76 2.70 T.C. 51.2 47.7 43.9 52.0 48.4 44.8 52.8 49.1 45.7 85 S.C. 33.1 32.1 30.6 35.4 34.5 32.6 37.7 36.8
ملخص المحتوى في الصفحة رقم 13
036-21004-002 Rev. B (0602) COOLING PERFORMANCE DATA AIR CONDITIONER MODEL NO. FRCS0601BF INDOOR COIL MODEL NO. G1FA060S21, 24 ID CFM 1600 1800 2000 CONDENSER ENTERING AIR ID DB 85 80 70 85 80 70 85 80 70 TEMPERATURE ID WB 72 67 57 72 67 57 72 67 57 T.C. 63.5 59.2 54.7 63.6 59.9 55.5 63.7 60.6 56.2 75 S.C. 42.2 40.8 39.1 43.5 42.1 40.3 44.7 43.4 41.5 K.W 3.18 3.16 3.12 3.19 3.17 3.13 3.20 3.17 3.14 T.C. 61.3 57.2 52.3 61.5 57.7 53.1 61.8 58.2 53.9 85 S.C. 41.7 40.2 37.9 42.9 41.4 39.1 44.2 42.7
ملخص المحتوى في الصفحة رقم 14
036-21004-002 Rev. B (0602) MATCHING INDOOR COMPONENTS ADD-ON COILS - FOR FURNACE APPLICATIONS G1NA G1UA UNCASED G1HD 1/2 CASED UPFLOW HORIZONTAL DUCT UPFLOW G2FD* MULTI-POSITION G1FA (UPFLOW, HORIZONTAL FULL CASED AND DOWNFLOW) UPFLOW * Available with factory installed horizontal drain pan. AIR HANDLERS - FOR NON-FURNACE APPLICATIONS N1AH OR N1VS MODULAR BLOWER (UPFLOW, HORIZONTAL AND DOWNFLOW) F2RC / F2FC OR G2FD F2RC / F2FP / F2FV COIL FAN COIL UNITS (UPFLOW, HORIZONTAL) 14 Unitary Products
ملخص المحتوى في الصفحة رقم 15
036-21004-002 Rev. B (0602) NOTES Unitary Products Group 15
ملخص المحتوى في الصفحة رقم 16
Subject to change without notice. Printed in U.S.A. 036-21004-002 Rev. B (0602) Copyright © by York International Corp. 2002. All rights reserved. Supersedes: 036-21004-002 Rev. A (0502) Unitary 5005 Norman Product York OK Group Drive 73069