ملخص المحتوى في الصفحة رقم 1
036-21528-003-A-0703
®
CHAMPION ULTRA
SINGLE PACKAGE
HEAT PUMPS
BHP024 THRU 048
2 THRU 4 NOMINAL TONS
13 SEER
FACTORY MOUNTED TXV
All units are completely wired, charged with R-22 and
DESCRIPTION
tested prior to shipment. Unique test sta
ملخص المحتوى في الصفحة رقم 2
036-21528-003-A-0703 CONDENSATE PAN TOP DISCHARGE A non-corrosive, long-lasting, water-tight pan is posi- The top discharge condenser fan does not disrupt tioned below the evaporator coil to collect and drain all neighboring areas and does not dry-out vegetation sur- condensate; less collection of stagnate condensate will rounding the unit. The warm air from the top mounted build-up. The condensate pan conforms to ASHRAE fan is blown up away from the structure and any land- 62-89 standards (V
ملخص المحتوى في الصفحة رقم 3
036-21528-003-A-0703 PROTECTED COMPRESSOR rate field accessories of single enthalpy and dual enthalpy are also available. The compressor is internally protected against high pressure and temperature. This is accomplished by the SINGLE ENTHALPY SENSOR simultaneous operation o
ملخص المحتوى في الصفحة رقم 4
036-21528-003-A-0703 RECTANGLE TO ROUND ADAPTERS unit mounted down shot applications. Includes hood and screen assembly. Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and WALL THERMOSTAT designed to fit over current duct openings on the base unit. Transition is from 15" square to 14" round. The units are designed to operate with 24-volt elec- tronic and electro-mechanical thermostats. All units ROOF CURBS can operate with single stage heat
ملخص المحتوى في الصفحة رقم 5
036-21528-003-A-0703 DIRECT DRIVE CONDENSER FAN MOTOR HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN INDOOR COIL HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN OUTDOOR COIL BACK AND BOTTOM RETURN AIR AND SUPPLY AIR DECORATIVE DUCT OPENING PROTECTIVE COIL GUARD HIGH VOL
ملخص المحتوى في الصفحة رقم 6
036-21528-003-A-0703 TABLE 3: COOLING CAPACITIES - 2 TON (BHP024) TEMPERATURE OF AIR ON INDOOR COIL 800 CFM 900 CFM TEMPERATURE AIR ON OUTDOOR COIL WB °F WB °F 72 67 62 57 72 67 62 57 NET CAP. MBH 29.1 26.0 23.8 23.4 29.7 26.6 24.3 23.9 POWER INPUT kW 1.93 1.91 1.88 1.87 1.95 1.93 1.91 1.90 86 19.2 23.1 23.8 23.4 20.9 25.1 24.3 23.9 83 16.9 20.8 23.8 23.4 18.3 22.5 24.3 23.9 85 °F 80 14.5 18.5 21.9 22.7 15.6 19.8 23.4 23.6 77 12.2 16.1 19.5 20.3 12.9 17.2 20.7 20.9 74 9.9 13.8 17.2 18.0 10.3 14.
ملخص المحتوى في الصفحة رقم 7
036-21528-003-A-0703 TABLE 4: COOLING CAPACITIES - 2-1/2 TON (BHP030) TEMPERATURE OF AIR ON INDOOR COIL 1000 CFM 1125 CFM TEMPERATURE AIR ON OUTDOOR COIL WB °F WB °F 72 67 62 57 72 67 62 57 NET CAP. MBH 34.1 31.5 28.4 29.9 35.4 32.7 29.5 31.0 POWER INPUT kW 2.52 2.48 2.44 2.43
ملخص المحتوى في الصفحة رقم 8
036-21528-003-A-0703 TABLE 5: COOLING CAPACITIES - 3 TON (BHP036) TEMPERATURE OF AIR ON INDOOR COIL 1050 CFM 1200 CFM TEMPERATURE AIR ON OUTDOOR COIL WB °F WB °F 72 67 62 57 72 67 62 57 NET CAP. MBH 41.1 37.5 34.5 34.3 42.4 38.6 35.5 35.3 POWER INPUT kW 2.89 2.81 2.73 2.73 3.00 2.91 2.83 2.82 86 25.6 32.3 34.5 34.3 28.2 35.5 35.5 35.3 83 22.5 29.3 33.5 33.6 24.7 32.0 35.5 35.3 85 °F 80 19.5 26.3 31.7 32.2 21.2 28.5 34.5 35.0 77 16.5 23.2 28.7 29.1 17.7 25.0 31.0 31.5 74 13.4 20.2 25.7 26.1 14.2
ملخص المحتوى في الصفحة رقم 9
036-21528-003-A-0703 TABLE 6: COOLING CAPACITIES - 3-1/2 TON (BHP042) TEMPERATURE OF AIR ON INDOOR COIL 1300 CFM 1400 CFM TEMPERATURE AIR ON OUTDOOR COIL WB °F WB °F 72 67 62 57 72 67 62 57 NET CAP. MBH 48.8 44.5 40.5 40.6 49.2 44.9 40.8 41.0 POWER INPUT kW 3.37 3.32 3.21 3.20
ملخص المحتوى في الصفحة رقم 10
036-21528-003-A-0703 TABLE 7: COOLING CAPACITIES - 4 TON (BHP048) TEMPERATURE OF AIR ON INDOOR COIL 1500 CFM 1600 CFM TEMPERATURE AIR ON OUTDOOR COIL WB °F WB °F 72 67 62 57 72 67 62 57 NET CAP. MBH 54.3 50.4 45.7 48.2 54.9 51.0 46.3 48.8 POWER INPUT kW 3.97 3.85 3.75 3.74 4.06 3.94 3.83 3.83 86 35.5 45.1 45.7 48.2 37.2 47.1 46.3 48.8 83 31.2 40.8 45.3 47.5 32.5 42.4 46.3 48.8 85 °F 80 26.8 36.4 43.7 45.2 27.8 37.8 45.3 46.9 77 22.5 32.0 39.3 40.9 23.2 33.1 40.6 42.3 74 18.1 27.7 35.0 36.5 18.5
ملخص المحتوى في الصفحة رقم 11
036-21528-003-A-0703 TABLE 8: HEATING CAPACITIES - 2 TON (BHP024) OUTDOOR AIR TEMPERATURE, °F (72% RH) 1 RETURN CAP CFM AIR °F & KW -10 0 10 20 30 40 50 60 MBH 10.216 11.748 13.601 15.843 18.554 21.834 25.801 30.601 55 KW 1.214 1.307 1.401 1.494 1.588 1.681 1.775 1.868 MBH 7.3
ملخص المحتوى في الصفحة رقم 12
036-21528-003-A-0703 TABLE 10: HEATING CAPACITIES - 3 TON (BHP036) OUTDOOR AIR TEMPERATURE, °F (72% RH) 1 RETURN CAP CFM AIR °F & KW -10 0 10 20 30 40 50 60 MBH 10.597 12.792 15.448 18.660 22.545 27.244 32.929 39.804 55 KW 1.791 1.898 2.005 2.112 2.219 2.326 2.433 2.540 MBH 9.420 11.615 14.271 17.483 21.368 26.067 31.752 38.627 900 70 KW 2.198 2.305 2.412 2.519 2.626 2.733 2.840 2.947 MBH 7.543 9.738 12.394 15.606 19.491 24.190 29.875 36.750 80 KW 2.476 2.583 2.690 2.797 2.904 3.011 3.118 3.225
ملخص المحتوى في الصفحة رقم 13
036-21528-003-A-0703 TABLE 12: HEATING CAPACITIES - 4 TON (BHP048) OUTDOOR AIR TEMPERATURE, °F (72% RH) 1 RETURN CAP CFM AIR °F & KW -10 0 10 20 30 40 50 60 MBH 13.911 17.096 21.021 25.859 31.821 39.170 48.226 59.388 55 KW 2.342 2.568 2.795 3.022 3.249 3.476 3.703 3.930 MBH 11
ملخص المحتوى في الصفحة رقم 14
036-21528-003-A-0703 1 TABLE 13: SIDE & BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT ) EXTERNAL STATIC PRESSURE - IWG MODEL NO. MOTOR SPEED UNIT 0.15 0.30 0.50 0.70 0.90 BHP SETTING AIRFLOW WATTS B1HP024 Cooling TB2-A, Heating TB2-A, Electric Heat 800 CFM 91 125 161 206 240 B1HP024 Cooling TB2-B, Heating TB2-B 900 CFM 118 148 199 243 285 B1HP030 Cooling TB2-A, Heating TB2-A, Electric Heat 1000 CFM 280 321 389 449 500 B1HP030 Cooling TB2-B, Heating TB2-B 1125 CFM 356 413 490 557 620 B1
ملخص المحتوى في الصفحة رقم 15
036-21528-003-A-0703 THERMOSTAT UNIT TERMINAL STRIP NOTE: ** = Minimum wire size of 18 AWG ** R R wire should be used for all field HEAT ANTICIPATOR installed 24 volt wire. SHOULD BE SET AT 0.25 G G AMPS FOR ALL MODELS Y Y * W W2 24 VOLT TRANSFORMER W1 PROGRAMMABLE THERMOSTAT
ملخص المحتوى في الصفحة رقم 16
036-21528-003-A-0703 TABLE 15: ELECTRICAL DATA (BASIC UNIT) VOLTAGE MAX. MAX OUTDOOR SUPPLY AIR COMPRESSOR 1 MINIMUM HACR UNIT LIMITATIONS FUSE MODEL POWER FAN BLOWER TRANSFORMER CIRCUIT BREAKER POWER SIZE, BHP SUPPLY MOTOR, MOTOR, SIZE (VA) AMPACITY SIZE, FACTOR 2 MIN. MAX. RLA LRA FLA FLA AMPS AMPS 024 208/230-1-60 187 253 9.3 57.0 1.1 5.0 17.7 25 25 0.96 40 208/230-1-60 187 253 15.0 72.5 1.1 5.0 24.9 35 35 0.96 40 030 208/230-3-60 187 253 10.0 63.0 1.1 5.0 18.6 25 25 0.96 75 460-3-60 414
ملخص المحتوى في الصفحة رقم 17
036-21528-003-A-0703 TABLE 16: ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT) COMPRESSOR SUPPLY ELECTRIC HEAT ACCESSORY MAX. MAX COND AIR MINIMUM 2 FUSE/ POWER FAN HACR BLOWER TOTAL CIRCUIT 1 SUPPLY RLA LRA MOTOR MODEL NO. KW SIZE, BREAKER MOTOR AMPS AMPACITY FLA AMPS SIZ
ملخص المحتوى في الصفحة رقم 18
036-21528-003-A-0703 TABLE 17: APPLICATION DATA BHP MODEL 024 030 036 042 048 COOLING 800 1000 1050 1300 1500 MINIMUM AIR FLOW (CFM) HEATING 800 1000 1050 1400 1400 COOLING 900 1125 1200 1400 1600 MAXIMUM AIR FLOW (CFM) HEATING 900 1125 1200 1500 1600 MINIMUM OPERATING TEMPERATURE IN COOLING MODE 45 45 45 45 45 (AMBIENT, °F) MIMINIM MIXED AIR IN COOLING MODE 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57 (RETURN AIR, DB °F/WB °F) MINIMUM MIXED AIR IN HEATING MODE 55 55 55 55 55 (RETURN AIR, °F) V D
ملخص المحتوى في الصفحة رقم 19
036-21528-003-A-0703 FIGURE 5 - UNIT DIMENSIONS Unitary Products Group 19
ملخص المحتوى في الصفحة رقم 20
036-21528-003-A-0703 FIGURE 6 - TYPICAL APPLICATIONS 20 Unitary Products Group