ملخص المحتوى في الصفحة رقم 1
FILE NO. A05-018
Revised : Nov. 2006
SERVICE MANUAL/INTEGRATION
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT
RAV-SM562UT-E RAV-SM562BT-E RAV-SM562CT-E
RAV-SM802UT-E RAV-SM802BT-E RAV-SM802CT-E
RAV-SM1102UT-E RAV-SM1102BT-E RAV-SM1102CT-E
RAV-SM1402UT-E RAV-SM1402BT-E RAV-SM1402CT-E
RAV-SP1102UT-E
• Service Manual for RAV-SM[[[KRT and RAV-SM[[[XT contact the Sales company or Dealer.
OUTDOOR UNIT
RAV-SM562AT-E RAV-SM802AT-E RAV-SM1102AT-E RA
ملخص المحتوى في الصفحة رقم 2
ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer. NOTE A direct curre
ملخص المحتوى في الصفحة رقم 3
7. REFRIGERANT R410A ............................................................................ 51 7-1. Safety During Installation/Servicing ............................................................... 51 7-2. Refrigerant Piping Installation....................................................................... 51 7-3. Tools .................................................................................................................. 55 7-4. Recharging of Refrigerant..................
ملخص المحتوى في الصفحة رقم 4
SAFETY CAUTION The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. [Explanation of indications] Indication Explanation Indicates contents assumed that an imminent danger causing a death or serious injury of DANGER the repair engineers and the third parties when an incorrect work ha
ملخص المحتوى في الصفحة رقم 5
WARNING Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Check earth wires. Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. Prohibition of modification. For spare parts, use those specified (∗ ∗ ∗ ∗ ∗). If unspecifi
ملخص المحتوى في الصفحة رقم 6
WARNING After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2MΩΩΩΩΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s Insulator check side. When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigeran
ملخص المحتوى في الصفحة رقم 7
New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner w
ملخص المحتوى في الصفحة رقم 8
4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below show
ملخص المحتوى في الصفحة رقم 9
1. SPECIFICATIONS 1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.3 7.1 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.42 – 7.72 11.32 – 10.37 16.30 – 16.00 19.20 – 17.60 Power consumption (kW) 1.76 2.34 3.52 4.09 Power factor (%) 95 94 98 97 Cooling E
ملخص المحتوى في الصفحة رقم 10
Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.3 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 7.17 – 6.57 8.95 – 8.21 11.24 – 10.31 16.51 – 15.14 Power consumption (kW) 1.53 1.93 2.40 3.56 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.46 3.68 4.17 3.51 Energy efficiency class * AA AA Energy ratin
ملخص المحتوى في الصفحة رقم 11
1-1-2. Concealed Duct Type Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.99 – 8.24 12.23 – 11.21 16.50 – 15.10 20.70 – 19.00 Power consumption (kW) 1.78 2.53 3.56 4.42 Power factor (%) 90 94 98 97 Cooling EER (W/W) 2.81 2.81 2.81 2.83 Energy efficiency cla
ملخص المحتوى في الصفحة رقم 12
Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.51 – 5.97 9.74 – 8.93 11.72 – 10.74 18.09 – 16.58 Power consumption (kW) 1.39 2.10 2.50 3.90 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.60 3.38 4.00 3.21 Energy efficiency class * AAA A Energy ratin
ملخص المحتوى في الصفحة رقم 13
1-1-3. Under Ceiling Type Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Model Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 5.0 7.0 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.71 – 7.98 12.23 – 11.21 16.20 – 14.90 21.18 – 19.40 Power consumption (kW) 1.82 2.53 3.51 4.52 Power factor (%) 95 94 98 97 Cooling EER (W/W) 2.75 2.77 2.85 2.72 Energy efficiency clas
ملخص المحتوى في الصفحة رقم 14
Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Model Outdoor unit RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.61 – 6.06 9.47 – 8.93 11.24 – 10.31 18.09 – 16.58 Power consumption (kW) 1.41 2.10 2.40 3.90 Power factor (%) 97 98 97 98 Cooling EER (W/W) 3.55 3.38 4.17 3.21 Energy efficiency class * AAA A Energy ratin
ملخص المحتوى في الصفحة رقم 15
1-1-4. Twin Type Type 4-Way Air Cassette Concealed Duct Under Ceiling Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Model Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 11.2 14.0 Indoor unit Indoor unit Power supply 1 phase 230V (220 – 24
ملخص المحتوى في الصفحة رقم 16
Type 4-Way Air Cassette Concealed Duct Under Ceiling Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Model Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 11.2 14.0 Indoor unit Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Ru
ملخص المحتوى في الصفحة رقم 17
1-2. Outdoor Unit Model name RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E 1 phase 230V (220 – 240V) Power supply 50Hz (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 1.1 1.6 2.5 3.0 Pole 4444 Refrigerant charged (kg) 1.0 1.7 2.8 2.8 Refrigerant control Pulse motor valve Standard length (m) 7.5 7.5 7.5 7.5 Min. length (m) 5.0 5.0 5.0 5.0 Max. total length (m) 30 30 50 50 Inter connecting pipe Additional refrigerant charge 20g/m 40g/m 4
ملخص المحتوى في الصفحة رقم 18
Model name RAV- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E 1 phase 230V (220 – 240V) Power supply 50Hz (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 2.0 2.0 3.75 3.75 Pole 4444 Refrigerant charged (kg) 1.5 2.1 2.95 2.95 Refrigerant control Pulse motor valve Standard length (m) 7.5 7.5 7.5 7.5 Min. length (m) 5.0 5.0 5.0 5.0 Max. total length (m) 50 50 70 70 Inter connecting pipe Additional refrigerant charge 20g/m 40g/m 40g/m 40g
ملخص المحتوى في الصفحة رقم 19
1-3. Operation Characteristic Curve • Operation characteristic curve RAV-SM562AT-E, RAV-SM802AT-E 14 16 14 12 RAV-SM802AT-E RAV-SM802AT-E RAV-SM802AT-E RAV-SM802AT-E 12 10 10 8 8 6 RAV-SM562AT-E RAV-SM562AT-E 6 RAV-SM562AT-E RAV-SM562AT-E 4 4 Conditions Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C 2 2 Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 0 0 0 20 40 60708090 100 0 204
ملخص المحتوى في الصفحة رقم 20
Operation characteristic curve RAV-SP562AT-E, RAV-SP802AT-E 14 16 14 12 RAV-SP802AT-E RAV-SP802AT-E 12 RAV-SP802AT-E RAV-SP802AT-E 10 10 RAV-SP562AT-E RAV-SP562AT-E 8 8 6 6 RAV-SP562AT-E RAV-SP562AT-E 4 4 Conditions Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C 2 2 Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 0 0 0 20406 500 70 80 100 0 204060 70 8090 100 Compressor sp