ملخص المحتوى في الصفحة رقم 1
A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-84 Lutron eLumen
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
ملخص المحتوى في الصفحة رقم 2
FS-8700-84_Lutron_eLumen Manual Table of Contents TABLE OF CONTENTS 1. Lutron eLumen Description .......................................................................................... 1 2. Driver Scope of Supply................................................................................................... 2 1.01 Supplied by FieldServer Technologies for this driver ............................................ 2 rd 1.02 Provided by the Supplier of 3 Party Equipment ...............
ملخص المحتوى في الصفحة رقم 3
FS-8700-84_Lutron_eLumen Manual Table of Contents 4.1.26. System Control Commands containing no Parameters: Toggle system variable value ....................................................................................................................... 20 4.1.27. System Control Commands containing no Parameters: Output temp scene 21 4.1.28. System Control Commands containing no Parameters: Select scene in area 22 4.1.29. System Control Commands containing no Parameters: Timeclock
ملخص المحتوى في الصفحة رقم 4
FS-8700-84_Lutron_eLumen Driver Manual Page 1 of 36 1. Lutron eLumen Description The Serial Lutron eLumen driver allows the FieldServer to transfer data to and from devices over RS-232 or RS-485 using eLumen protocol. The FieldServer can only be used operationally as a Lutron Client driver. Any existing Lutron Server drivers are for FieldServer testing purposes only and cannot be used to emulate a Lutron eLumen system. The driver supports the following 3 panels: GRAFIK5000, G
ملخص المحتوى في الصفحة رقم 5
FS-8700-84_Lutron_eLumen Driver Manual Page 2 of 36 2. Driver Scope of Supply 1.01 Supplied by FieldServer Technologies for this driver FieldServer Technologies Description PART # FS-8915-10 UTP cable (7 foot) for RS-232 use FS-8917-02 RJ45 to DB9F connector adapter FS-8700-84 Driver Manual. rd 1.02 Provided by the Supplier of 3 Party Equipment rd 2.1.1. Required 3 Party Hardware Part # Description Lutron Panel FieldServer Technologies 1991 Tarob Court Milpitas, Californ
ملخص المحتوى في الصفحة رقم 6
FS-8917-02 FS-8700-84_Lutron_eLumen Driver Manual Page 3 of 36 3. Hardware Connections The FieldServer is connected to the Lutron eLumen as shown in connection drawing. Configure the eLumen according to manufacturer’s instructions FS-8917-02 LUTRON SERIAL RS-232 INTERFACE PART # 470-784 8917-02 WIRE LIST CAT 5 CABLE FS-8915-10 FUNCTION FROM TO COLOUR RX RJ45-01 DB9M-02 WHITE CTS RJ45-02 DB9M-08 BROWN DSR RJ45-03 DB9M-06 YELLOW GND RJ45-04 DB9M-05 GREEN GND RJ45-05 RED DTR RJ45-06 DB9
ملخص المحتوى في الصفحة رقم 7
FS-8700-84_Lutron_eLumen Driver Manual Page 4 of 36 120V 15A Dedicated Control Feed Wallstation link To control stations eLumen Aux Link (RS-485) Processor User Interface link Dimmer panel link To dimmer panels Inter-processor link Serial Power OK Tx Rx Tx Rx - + EIA232 Ethernet USB EIA485 FS-B2010 (408)-262-2299 LUTRON ELUMEN RS-485 CONNECTION DIAGRAM BASE NAME: DATE: 11/12/04 FILE NAME: FS-T28700-84 .VSD BY: MC FieldServer Tech
ملخص المحتوى في الصفحة رقم 8
FS-8700-84_Lutron_eLumen Driver Manual Page 5 of 36 4. Configuring the FieldServer as a Lutron eLumen Client For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). This section documents and describes the parameters necessary fo
ملخص المحتوى في الصفحة رقم 9
FS-8700-84_Lutron_eLumen Driver Manual Page 6 of 36 1.04 Client Side Connection Descriptions Section Title Connections Column Title Function Legal Values Specify which port the 1 Port device is connected to the P1-P8, R1-R2 FieldServer Protocol Specify protocol used eLumen Baud* Specify baud rate 9600 – Vendor limitation Parity* Specify parity None Data_Bits* Specify data bits 8 Stop_Bits* Specify stop bits 1 Specify hardware Handshaking* None handshaking Poll _Delay* Ti
ملخص المحتوى في الصفحة رقم 10
FS-8700-84_Lutron_eLumen Driver Manual Page 7 of 36 Example // Client Side Nodes Nodes Node_Name, Node_ID, Protocol, Connection, Node_type LUT_GRF6_0, 17, eLumen, P1, hex 1.06 Client Side Map Descriptors The driver uses Map Descriptors with Lutron commands to build poll messages that will be sent to the eLumen system. Example Map Descriptors are shown in the next section. Note the following in the use of Map Descriptors for the Lutron driver: Lutron command
ملخص المحتوى في الصفحة رقم 11
FS-8700-84_Lutron_eLumen Driver Manual Page 8 of 36 4.1.1. FieldServer Related Map Descriptor Parameters Column Title Function Legal Values Name of this Map Up to 32 alphanumeric Map_Descriptor_Name Descriptor characters Name of Data Array One of the Data Array where data is to be Data_Array_Name names from “Data Array” stored in the section above FieldServer 0 to maximum specified in Starting location in Data_Array_Location “Data Array” section Data Array above Functio
ملخص المحتوى في الصفحة رقم 12
FS-8700-84_Lutron_eLumen Driver Manual Page 9 of 36 Column Title Function Legal Values Any Data Array name. If Name of Data Array that not listed under Data contains a list of zones DA_Lut_List Arrays the driver will or areas, etc, needed to auto-create the Data build the poll message. Array. The offset into the DA_Lut_List Data Array 0 to the maximum offset where the driver will DA_Lut_List_Offset into the DA_Lut_List retrieve the list data Data Array. when building th
ملخص المحتوى في الصفحة رقم 13
FS-8700-84_Lutron_eLumen Driver Manual Page 10 of 36 Column Title Function Legal Values Any Data Array name. If Name of Data Array not listed under Data DA_Zone_Names where retrieved zone Arrays the driver will names will be stored. auto-create the Data Array. The offset into the 0 to the maximum offset DA_Zone_Names Data DA_Zone_Names_Offse into the Array where retrieved t DA_Zone_Names Data zone names will be Array. stored. Start and end numbers Area_Names_Start of ar
ملخص المحتوى في الصفحة رقم 14
FS-8700-84_Lutron_eLumen Driver Manual Page 11 of 36 4.1.4. System Monitor Command – Time Now // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Length Time_now, 5s, Time_now, 0, rdbc, LUT_GRF6_0, time_now, 1 Data storage in Data Array Position from offset Description: 0 Minutes from midnight 4.1.5. System Monitor Command – Astro Times // Client side Ma
ملخص المحتوى في الصفحة رقم 15
FS-8700-84_Lutron_eLumen Driver Manual Page 12 of 36 4.1.6. System Monitor Command – Date // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Length Date, 5s, Date, 0, rdbc, LUT_GRF6_0, date, 4 Data storage in Data Array Position from offset Description: 0 Month ( 1-12 ) 1 Day of month ( 1-31 ) 2 Year ( 0-99 ) 3 Day of week ( 1-7, 1=Sunday ) 4.1.7. System
ملخص المحتوى في الصفحة رقم 16
FS-8700-84_Lutron_eLumen Driver Manual Page 13 of 36 4.1.9. System Monitor Command – Serial Number // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Length Serial_num, 5s, Serial_num, 0, rdbc, LUT_GRF6_0, serial_no, 1 Data storage in Data Array Position from offset Description 0 Serial number 4.1.10. System Monitor Command – Area Status // Client side
ملخص المحتوى في الصفحة رقم 17
FS-8700-84_Lutron_eLumen Driver Manual Page 14 of 36 4.1.11. System Monitor Command – Timeclock Status // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Area, Length Tclk_sts_00, 1s, Tclk_status, 0, rdbc, LUT_GRF6_0, timeclock_status, 0, 4 Tclk_sts_01, 1s, Tclk_status, 4, rdbc, LUT_GRF6_0, timeclock_status, 1, 4 Data storage in Data Array Position from off
ملخص المحتوى في الصفحة رقم 18
FS-8700-84_Lutron_eLumen Driver Manual Page 15 of 36 4.1.13. System Monitor Command – Request Panel Emergency Status // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, Panel, Length Pnl_emerg_sts_00, 1s, Pnl_emerg_sts, 0, rdbc, LUT_GRF6_0, pnl_emerg_status, 0, 1 Pnl_emerg_sts_511, 1s, Pnl_emerg_sts, 511, rdbc, LUT_GRF6_0, pnl_emerg_status, 511, 1 Data storag
ملخص المحتوى في الصفحة رقم 19
FS-8700-84_Lutron_eLumen Driver Manual Page 16 of 36 4.1.15. System Monitor Command – Wallstation Status // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, link, link_station, Length Wall_st_sts_0000, 1s, Wall_st_sts_00, 0, rdbc, LUT_GRF6_0, wallstation_status, 0, 0, 32 Wall_st_sts_0001, 1s, Wall_st_sts_00, 32, rdbc, LUT_GRF6_0, wallstation_status, 0, 1, 32
ملخص المحتوى في الصفحة رقم 20
FS-8700-84_Lutron_eLumen Driver Manual Page 17 of 36 4.1.17. System Control Commands containing no Parameters: – Halt Zone // Client side Map Descriptors Map_Descriptors Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, GRAFIK_command, DA_Lut_List, DA_Lut_List_Offset, Length Zone_halt, Lut_triggers, 0, awt, LUT_GRF6_0, halt_zone, Zone_list, 0, 1 DA_Lut_List data setup Position from DA_Lut_List_Offset Description 0-63 Zone(s) to hal