                        FS-8700-83 Gamewell         Index  TABLE OF CONTENTS    1. GAMEWELL SERIAL DRIVER DESCRIPTION ...................................................................................1  2. DRIVER SCOPE OF SUPPLY ..............................................................................................................1  2.1 SUPPLIED BY FIELDSERVER TECHNOLOGIES FOR THIS DRIVER ............................................................1  2.2 PROVIDED BY USER.........................................
                    
                    ملخص المحتوى في الصفحة رقم 3 
                    
                        FS-8700-83 Gamewell         Page 1 of 24  1.  Gamewell Serial Driver Description     The Gamewell Serial Driver allows the FieldServer to accept messages generated by a  Gamewell 600 Series Panel as well as ‘Smartnet Data Stream’ messages generated by a  Gamewell Smartnet terminal.    All Gamewell 600 Series Fire Alarm panels are equipped with a serial port, which produces  panel, circuit or device status messages. This driver is designed to process these messages  and store this status informat
                    
                    ملخص المحتوى في الصفحة رقم 4 
                    
                        FS-8700-83 Gamewell         Page 2 of 24    3. Hardware Connections    The bridge is connected to the Gamewell panel as shown below.    Configure the Gamewell panel according to manufacturer’s instructions      FIELDSERVER RS232 PORT GAMEWELL SIM 232 RJ45-01 FS-8915-10 BOARD BROWN XMT COM COM2 RCV GND RJ45-04 BLUE/WHITE RJ45-08 ORANGE/WHITE (408)-262-2299 GAMEWELL CONNECTION DIAGRAM BASE NAME: DATE:6/4/02 FILE NAME:   T28700-83 .VSD BY:       MN FieldServer Technologies 1991 Tarob Court Milpitas
                    
                    ملخص المحتوى في الصفحة رقم 5 
                    
                        FS-8700-83 Gamewell         Page 3 of 24  4. Configuring the FieldServer as a Gamewell Serial Driver Client  For a detailed discussion on FieldServer configuration, please refer to the FieldServer  Configuration Manual. The information that follows describes how to expand upon the factory  defaults provided in the configuration files included with the FieldServer (See “.csv” files on the  driver diskette).    This section documents and describes the parameters necessary for configuring the Field
                    
                    ملخص المحتوى في الصفحة رقم 6 
                    
                        FS-8700-83 Gamewell         Page 4 of 24  4.2 Client Side Connections    Section Title  Connections  Column Title Function Legal Values  Port Specify which port the device is P1-P8, R1-R2  connected to the Bridge  Baud Specify baud rate 2400    The driver supports all standard  baud rates 110 – 115200.  Gamewell panels only support a  baud rate of 2400.  Parity* Specify parity None    The driver supports the following  options. Even, Odd, None, Mark,  Space    The Gamewell panels only  support t
                    
                    ملخص المحتوى في الصفحة رقم 7 
                    
                        FS-8700-83 Gamewell         Page 5 of 24  4.3 Client Side Nodes    Section Title  Nodes  Column Title Function Legal Values  Node_Name Provide name for node Up to 32 alphanumeric  characters  Node_ID Gamewell panel node address. 0-256      The Node Id has no meaning  when the FieldServer is  connected directly to Gamewell  panel.  When connecting to a  Gamewell panel directly always  set the Node_ID to zero. When  connecting to a Gamewell  SmartNet terminal. The  Node_ID is important and  should
                    
                    ملخص المحتوى في الصفحة رقم 8 
                    
                        FS-8700-83 Gamewell         Page 6 of 24  4.4 Client Side Map Descriptors  FieldServer Related Map Descriptor Parameters    Column Title Function Legal Values  Map_Descriptor_Name Name of this Map Descriptor Up to 32 alphanumeric  characters  Data_Array_Name Name of Data Array where data One of the Data Array names  is to be stored in the Bridge from “Data Array” section above  Data_Array_Location Starting location in Data Array 0 to maximum specified in  “Data Array” section above  Function Fun
                    
                    ملخص المحتوى في الصفحة رقم 9 
                    
                        FS-8700-83 Gamewell         Page 7 of 24    Length Length of Map Descriptor 1 – 1000    Controls how many elements of the data  array are controlled by the map  descriptor.  Address This commonly used parameter has no 0  meaning for this driver. If specified it is  best set to zero.  Ckt Specify the circuit number whose Panel , 1 ,2 , 3 …. 131  message will get stored using this map  descriptor.    Use the keyword ‘Panel’ if the you wish  to store data from a panel. All messages  which do not co
                    
                    ملخص المحتوى في الصفحة رقم 10 
                    
                        FS-8700-83 Gamewell         Page 8 of 24  Map Descriptor Example 1 – Store data from incoming messages.  This example illustrates typical map descriptor uses to store data from panel generated messaged.     As all these map descriptors have their Clear_On_Reset field set to yes, when a panel reset message is received all the data in the controlled  arrays will be set to zero When a point reports its own  state as normal the driver will set the appropriate element of the appropriate array to zero
                    
                    ملخص المحتوى في الصفحة رقم 11 
                    
                        FS-8700-83 Gamewell         Page 9 of 24    Map Descriptor Example 2 – Send a Reset / Ack / Silence Command.  This example illustrates three map descriptors used to send commands to the panel. These are the only active map descriptors that can be used  with the Gamewell Serial Driver.     st These map descriptors use the WRBX function. When the 1 element (because Data_Array_Offset = 0 ) has its value updated, even if the value  doesn’t change, then the driver will send the command to the panel. 
                    
                    ملخص المحتوى في الصفحة رقم 12 
                    
                        FS-8700-83 Gamewell         Page 10 of 24  5. Configuring the FieldServer as a Gamewell Serial Driver Server    The Gamewell Serial Driver provides limited server functionality. This has been developed to allows for  automated testing and Quality Assurance. It is not supported or documented however, at a client’s  request it can be extended & documented (typically at an additional cost.)    6. Advanced Topics    6.1 Driver Limitations & Exclusions    The driver does not support scaling when data
                    
                    ملخص المحتوى في الصفحة رقم 13 
                    
                        FS-8700-83 Gamewell         Page 11 of 24    1. If the Data Type is ‘Any’ then the map descriptor will be used to store data from message with  any status.      2. The state reported is filtered and must match the Data_Type for the associated array to be  updated. For example, if the Data_Type of a MapDesc is ‘Alarms’ and a message is received that  reports a Fault then the map descriptor will not be used to store the data from the message.    3. Normally, user’s are interested in the Status of 
                    
                    ملخص المحتوى في الصفحة رقم 14 
                    
                        FS-8700-83 Gamewell         Page 12 of 24    When comparing these keywords to the data in the Status field of the message the driver only  compares the first three characters. The comparison is case insensitive.  Adding a New Status Type    The fragment of a CSV file displayed below illustrates how to change the value associated with  ‘BUS’ to 9 and adds two new Status types, Fred and Ginger.        Driver_Table    Gamewell_Status_String, Gamewell_Status_Value, Protocol   BUS                   ,
                    
                    ملخص المحتوى في الصفحة رقم 15 
                    
                        FS-8700-83 Gamewell         Page 13 of 24    Based on the table below if a message contains the string ‘Fire Alarm in’ then the action number  will be stored as 11.      Value Action Description  255  Driver did not recognize action type    System Setup   1 Skip System I/O Assignments  System power up  2 Begin System I/O Assignments  System programming itself  Ignore any data from this point until "Exit Program  3 Programming Mode Entered  Mode" is received  4 Exit Program Mode  See Programming 
                    
                    ملخص المحتوى في الصفحة رقم 16 
                    
                        FS-8700-83 Gamewell         Page 14 of 24  33 New Card Detected @  System Problem  34 Out of Memory Assigning    System Problem  Supervisory or trouble in circuit that automatically  35 I/O Restored   restore themselves  36 Trouble Tested in    System Problem  37 Trouble in  System Problem  38 Output Shorted in    System Problem  39 Dup. Dev. in   System Problem  40 Dev. Missing in   System Problem  41 Type Mismatch  System Problem  42 Dev. Dirty in  System Problem  43 No Response from Analog CK
                    
                    ملخص المحتوى في الصفحة رقم 17 
                    
                        FS-8700-83 Gamewell         Page 15 of 24    Adding new Action Types    The following fragment from a CSV file shows how you can add two new action types. If a  message is received and its action field contains the text ‘FRED’ then the action number will be  stored as 100.      Driver_Table    Gamewell_Action_String, Gamewell_Action_Value, Protocol    FRED                  , 100                  , Gamewell    GINGER                , 101                  , Gamewell        The driver can store a m
                    
                    ملخص المحتوى في الصفحة رقم 18 
                    
                        FS-8700-83 Gamewell         Page 16 of 24  6.6 Advanced Map Descriptor Examples  Example 1 : Filtering Data  You can direct the driver to filter the incoming messages so that data arrays are only updated for particular states. For example an incoming  messge which reports a device in Ckt 1 to be in a FAULT state (Status:FAULT) will use the map descriptor ‘Ckt1_data03’ to store the data and the  array DA_FAULTS1 will be updated. If however, the message reported an ALARM state (Status:ALARM) then 
                    
                    ملخص المحتوى في الصفحة رقم 19 
                    
                        FS-8700-83 Gamewell         Page 17 of 24    Example 2 : Action Numbers    You can have the driver store a value corresponding to the contents of the action field reported in the incoming messages. Actions are brief  descriptions of the event that caused the message to be generated. A table of values vs. descriptions is provided in section 6.5. The driver stores  the most recent action number, overwriting the previously stored action numbers. The driver does not keep an event log.  The action nu
                    
                    ملخص المحتوى في الصفحة رقم 20 
                    
                        FS-8700-83 Gamewell         Page 18 of 24    Example 3 : Action Bits  Instead of having the driver store a value to indicate the action, the driver can set a bit, whose offset indicates the underlying action. For example,  if the string ‘Fire Alarm in’ is contained in the action field of the message the driver would set the array element at offset 11  (use table 6.5 to get  the value vs. string) to 1.    Important to note is that the driver does not clear a previously set bit when a new action i