ملخص المحتوى في الصفحة رقم 1
DVPDNET-SL
DeviceNet Network Scanner
Operation Manual
DVP-0204520-02
ملخص المحتوى في الصفحة رقم 2
ملخص المحتوى في الصفحة رقم 3
DeviceNet Network Scanner DVPDNET-SL Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages on the device or injuries to staff. Switch off the power before wiring. DVPDNET-SL is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or speci
ملخص المحتوى في الصفحة رقم 4
DeviceNet Network Scanner DVPDNET-SL 3.2 Installing DVPDNET-SL and DVP-SV MPU on DIN Rail.............................................. 7 3.3 Connecting to DeviceNet Connection Port .................................................................. 8 4 CONFIGURATION ................................................................................................................. 8 4.1 Corresponding Relation between DVPDNET-SL and DVP-SV.................................... 8 4.2 I/O Mapping T
ملخص المحتوى في الصفحة رقم 5
DeviceNet Network Scanner DVPDNET-SL 1 Introduction 1. To ensure correct installation and operation of DVPDNET-SL, please read this chapter carefully before using your DVPDNET-SL. 2. This chapter only provides introductory information on DVPDNET-SL. For more detailed information on DeviceNet protocol, please refer to relevant references or literatures. 3. DVPDNET-SL is a DeviceNet master module operating on the left side of DVP-SV series PLC MPU. When DVP-SV is connected to DeviceNet thr
ملخص المحتوى في الصفحة رقم 6
DeviceNet Network Scanner DVPDNET-SL 1.3 I/O Scan List Item Explanation Software screen Before DVPDNET-SL starts its operation, you have to configure its scan list through the configuration software. The scan list is a list consisting of the information of slave devices with data, e.g. slave address, I/O type, I/O data length and so on, to be exchanged with DVPDNET-SL. Scan Table DVPDNET-SL is responsible for managing the slave devices in the scan list, establishing connections and
ملخص المحتوى في الصفحة رقم 7
9 9 8 8 7 7 6 6 DeviceNet Network Scanner DVPDNET-SL Electrical specification Voltage 11 ~ 25 VDC supplied by the power cable in the network Current 28mA (typical), 125mA impulse current (24 VDC) Environment ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV Noise immunity Analog & Communication I/O: 1KV Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m O
ملخص المحتوى في الصفحة رقم 8
9 9 8 8 7 7 6 6 DeviceNet Network Scanner DVPDNET-SL 2.3 DeviceNet Connection Port The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with DVPDNET-SL. PIN Signal Color Content 1 V- Black 0 VDC 5 4 2 CAN_L Blue Signal- 3 3 SHIELD - Shielded 2 1 4 CAN_H White Signal+ 5 V+ Red 24 VDC 2.4 Address Switch The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are forbidden). 5 Switch setting Content
ملخص المحتوى في الصفحة رقم 9
DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL. When DVPDNET-SL is operating, changing the setting of the function switch will be invalid. Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch. 2.6 Digital Indicator The digital indicator provides the following two functions: DVPDNET POWER MS NS 1. Displaying the node address and error messages of DVPDNET-SL and error messages. 2. Displaying the error message of slave. 2.7 I/O Module Connection Por
ملخص المحتوى في الصفحة رقم 10
DeviceNet Network Scanner DVPDNET-SL DVPDNET DVP28SV 35mm DIN rail RUN STOP 3.3 Connecting to DeviceNet Connection Port The colors on the PINs on the DeviceNet connection port match the colors of the connection cables. Make sure you connect the cable to the right PIN. We recommend you also apply Delta’s power module in the connection. 4 Configuration 4.1 Corresponding Relation between DVPDNET-SL and DVP-SV After all DVPDNET-SL are connected to DVP-SV, DVP-SV will distribute data map
ملخص المحتوى في الصفحة رقم 11
DeviceNet Network Scanner DVPDNET-SL Mapped D registers DVPDNET-SL index Output mapping Input mapping 4 D7750 ~ D7997 D7500 ~ D7747 5 D8250 ~ D8497 D8000 ~ D8247 6 D8750 ~ D8997 D8500 ~ D8747 7 D9250 ~ D9497 D9000 ~ D9247 8 D9750 ~ D9997 D9500 ~ D9747 4.2 I/O Mapping Table Output mapping are Input mapping area D register Mapping area Data length D register Mapping area Data length Explicit message Explicit message D6250 ~ D6281 32 words D6000 ~ D6031 32 words program request progra
ملخص المحتوى في الصفحة رقم 12
DeviceNet Network Scanner DVPDNET-SL DVP-PS01 DVPDNET-SL DVP28SV DVPDNET DVP28SV DeviceNet network configuration tool L N RUN 0V STOP Node 01 RS-232 DeviceNet Node 03 Node 02 X0 X1 PORT1 PORT2 L Y0 N 0V IFD9502 DVP-PS01 RTU-DNET DVP-16SP VFD-B 2. Set up DVPDNET-SL, DNA01 and RTU-DNET according to the table below. Module Node address Baud rate DVPDNET-SL 01 500 kbps IFD9502 02 500 kbps RTU-DNET 03 500 kbps 5.2 How to Configure Network by DeviceNet Network Configuration Tool 1.
ملخص المحتوى في الصفحة رقم 13
DeviceNet Network Scanner DVPDNET-SL (3) Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud rate and communication format. Item Function Default COM port on the PC to be used to communicate with COM Port COM1 DVP-SV Address Communication address of DVP-SV 01 Baud rate Communication speed between the PC and DVP-SV 9,600 (bps) Data Bits 7 Communication protocol between the PC and DVP-SV Parity Even Parity Stop Bit 1 Mode Communicatio
ملخص المحتوى في الصفحة رقم 14
DeviceNet Network Scanner DVPDNET-SL (5) Click on “OK”, and DeviceNetBuilder will start to scan the entire network. (6) If the bar on the dialog box does not progress, it means the connection between the PC and DVP-SV is abnormal, or there are other programs also using the COM port on the PC. After the scan is completed, the dialog box will tell you that the scan is completed, and the icons and device names of all the nodes scanned on the network will be shown on the screen. See the fig
ملخص المحتوى في الصفحة رقم 15
DeviceNet Network Scanner DVPDNET-SL (8) Click on “IO Configure…” button in “Node Configuration” dialog box, and you will then see “RTU Configuration” page. (9) Click on “Scan IO”, and the "Warning” dialog box will appear. (10) Click on “OK”. DeviceNetBuilder will then detect the special I/O module connected to RTU-DNET and the number of points in the digital I/O module and display the information on "RTU Configuration” page. DVP-PLC Operation Manual 13
ملخص المحتوى في الصفحة رقم 16
DeviceNet Network Scanner DVPDNET-SL (11) Double click on RTU-DNET icon, and you will then see “RTU Setup” dialog box. (12) Set up the parameters in RTU-DNET and confirm its I/O information. Item Function Default The sum of the length of the status word of RTU-DNET and the input data of the I/O module connected to it. The status Input IO word of RTU-DNET occupies 2 bytes. One input channel of N/A Data Length the special I/O module occupies 2 bytes. 8 points of the digital input are
ملخص المحتوى في الصفحة رقم 17
DeviceNet Network Scanner DVPDNET-SL Item Function Default The digital output points shall be 8’s multiple. The number will DIDO Output be regarded as 8 when it is less than 8 and regarded as 16 N/A Points (Y) when it is bigger than 8 but less than 16. The number of special I/O modules connected to RTU-DNET. AIAO Module N/A Number Range: 0 ~ 8 The interval when RTU-DNET executes diagnosis. Range: Diagnostic 5 (sec) Intervel Time 1~ 65 secs How RTU-DNET will react when the speci
ملخص المحتوى في الصفحة رقم 18
DeviceNet Network Scanner DVPDNET-SL (16) Confirm the parameters and I/O data in VFD-B and click on “OK”. 2. Configuration of DVPDNET-SL (1) Double click on DNET Scanner (node 01), and the “Scan Module Configuration..." dialog box will appear. You can find the currently available nodes, RTU-DNET and VFD-B Drives 230V 3HP, in the list on the left side. On the right side, there is an empty “Scan List”. (2) Move the slave devices on DeviceNet in the "Available Nodes” list on the left side
ملخص المحتوى في الصفحة رقم 19
DeviceNet Network Scanner DVPDNET-SL (3) Confirm all the settings and click on “OK”. Next, download the configuration to DVPDNET-SL. If DVP-SV is in RUN mode while you are downloading the configuration, a “Warning” dialog box will appear. (4) Click on “OK” to continue the download. Make sure DVP-SV is in RUN mode. Follow the steps given above to configure DeviceNet network. If the I/O data do not include control word and status word of RTU-DNET, the I/O data mapping of DVPDNET-SL and
ملخص المحتوى في الصفحة رقم 20
DeviceNet Network Scanner DVPDNET-SL Slave → DVPDNET-SL Register in Devices in slave DVPDNET-SL D6037H Digital I/O module X0 ~ X7 on DVP-16SP D6037L N/A D6038H Status of LED on VFD-B D6038L Status of VFD-B AC motor drive D6039H High byte of frequency in VFD-B D6039L Low byte of frequency in VFD-B If the I/O data include control word and status word of RTU-DNET, the I/O data mapping of DVPDNET-SL and its slave devices will be: DVPDNET-SL → slave Register in Devices in slave