ملخص المحتوى في الصفحة رقم 1
INSTALLATION GUIDE FOR THE
ELECTRIC FIREPLACE
MODEL NUMBERS:
BF33ST/DX
BF39ST/DX
BF45ST/DX
7206350200REV06
ملخص المحتوى في الصفحة رقم 2
CONTENTS PAGE 1 Listings and Code Approvals PAGE 1 Model Specifications PAGE 1 Step-by-Step Installation Section A PAGE 2 Framing Section B PAGE 2 Recommended Power Supply Wire Specifications PAGE 2 Recommended Wire and Fusing Requirements PAGE 3 Voltage Selector Switch Location PAGE 3 Mounting Flanges Section C PAGE 4 Factory Setting Wiring 240 Volt (Without Main Power Wall Switch) PAGE 5 Factory Setting Wiring 120 volt (Wit
ملخص المحتوى في الصفحة رقم 3
LISTINGS AND CODE APPROVALS The BF series fireplaces have been tested in accordance with the UL 2021 and CSA C22.2 No. 46 standards for fixed and location-dedicated electric room heaters. MODEL SPECIFICATIONS AMPS AMPS AMPS AMPS Model Remote Wall Refractory Description Voltage Volts Rated Power Watts No Heat 120 208 240 Number Control Thermostat Brick Look Volt Volt 120 Volt Volt 33” 120/120/208/ 245/1440/2100/ BF33ST Option Option N/A 2.0 12.0 10.10 11.25 Standard 240 2700
ملخص المحتوى في الصفحة رقم 4
WARNING Ensure method of installation does NOT obscure the air intake slots on bottom front of unit in any manner. (see diagram in Section A) SECTION A: FRAMING Dimensions MODEL A B C D E F G H I J K L BF33ST/DX 15.0” 33.5” 29.5” 23.0” 14.3” 29.6” 32.8” 18.8” 28.5” 48.0” 34.0” 34.0” BF39ST/DX 16.0” 39.5” 33.5” 26.6” 15.3” 36.0” 38.7” 22.8” 32.7” 54.0” 38.0” 38.0” BF45ST/DX 16.0” 45.5” 33.5” 26.6” 15.3” 42.0” 44.7” 22.8” 32.7” 60.0” 42.0” 42.0” Top Surface
ملخص المحتوى في الصفحة رقم 5
VOLTAGE SELECTOR SWITCH LOCATION IMPORTANT: Ensure that the incoming power supply voltage matches the setting of the voltage selector switch. NOTE: The voltage selector switch is located inside the exhaust panel on the top right hand corner. CAUTION: When changing the voltage selector switch from 240 volts to 120 volts ensure that the power supply is turned FIGURE 1 off. NOTE: Carefully insert a flat headed screwdriver inside the exhaust panel to change the switc
ملخص المحتوى في الصفحة رقم 6
SECTION C: FACTORY SETTING WIRING (WITHOUT MAIN POWER WALL SWITCH) IMPORTANT: The unit is factory configured for 208/240 volt operation NOTE: Use 3 conductor wire with ground (4 wires total) from the power supply (breaker panel) to the junction box on the unit. NOTE: All wiring must be completed prior to installing the unit. NOTE: Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit to the power supply.
ملخص المحتوى في الصفحة رقم 7
SECTION C: FACTORY SETTING WIRING (WITHOUT MAIN POWER WALL SWITCH) IMPORTANT: The unit is factory configured for 208/240 volt operation NOTE: Use 2 conductor wire with ground (3 wires total) from the power supply (breaker panel) to the junction box on the unit. NOTE: All wiring must be completed prior to installing the unit. NOTE: Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit to the power supply.
ملخص المحتوى في الصفحة رقم 8
SECTION C: FACTORY SETTING WIRING (WITHOUT MAIN POWER WALL SWITCH) (NO HEAT INSTALLATION) IMPORTANT: The unit is factory configured for 208/240 volt operation NOTE: Use 2 conductor wire with ground (3 wires total) from the power supply (breaker panel) to the junction box on the unit. NOTE: All wiring must be completed prior to installing the unit. NOTE: Ensure that the voltage selector switch is in the proper position for the required supply voltage prior to connecting the unit t
ملخص المحتوى في الصفحة رقم 9
SECTION D: MAIN POWER WALL SWITCH WIRING OPTIONS MAIN POWER WALL SWITCH WIRING FOR 240 VOLT NOTE: This option should not be used with the remote control kit. NOTE: Before installing the unit you must have the following wires installed: 1. A 3 conductor wire with ground (4 wires total) from the power supply panel to the main switch wall box. 2. A 3 conductor wire with ground (4 wires total) from the main switch wall box to the junction box on the unit. NOTE: Use a double
ملخص المحتوى في الصفحة رقم 10
240 VOLT MAIN WALL SWITCH WIRING DIAGRAM WHITE - N WHITE – N 240 V RED – L2 RED – L2 POWER SUPPLY WALL SWITCH BLACK – L1 BLACK – L1 (BREAKER PANEL) GROUND - G GROUND - G 8 FIREPLACE JUNCTION BOX
ملخص المحتوى في الصفحة رقم 11
MAIN POWER WALL SWITCH WIRING FOR 120 VOLT NOTE: This option should not be used with the remote control kit. NOTE: Before installing the unit have the following wires installed: 1. A 2 conductor wire with ground (3 wires total) from the power supply panel to the main switch wall box. 2. A 2 conductor wire with ground (3 wires total) from the main switch wall box to the junction box on the unit. NOTE: Use a single pole, single throw (on/off) wall switch that is rated for a minimu
ملخص المحتوى في الصفحة رقم 12
120 VOLT MAIN WALL SWITCH WIRING DIAGRAM WHITE - N WHITE – N RED – L2 120 V POWER BLACK – L1 SUPPLY (BREAKER WALL BLACK – L1 PANEL) SWITCH GROUND - G GROUND - G 10 FIREPLACE JUNCTION BOX
ملخص المحتوى في الصفحة رقم 13
MAIN POWER WALL SWITCH WIRING FOR 120 VOLT NO HEAT INSTALLATION NOTE: This option should not be used with the remote control kit. NOTE: Before installing the unit have the following wires installed: 3. A 2 conductor wire with ground (3 wires total) from the power supply panel to the main switch wall box. 4. A 2 conductor wire with ground (3 wires total) from the main switch wall box to the junction box on the unit. NOTE: Use a single pole, single throw (on/off) wall switch that
ملخص المحتوى في الصفحة رقم 14
120 VOLT MAIN WALL SWITCH WIRING DIAGRAM NO HEAT INSTALLATION WHITE - N WHITE – N RED – L2 120 V Wire Nut POWER BLACK – L1 SUPPLY (BREAKER WALL BLACK – L1 PANEL) SWITCH GROUND - G GROUND - G 12 FIREPLACE JUNCTION BOX
ملخص المحتوى في الصفحة رقم 15
SECTION E: HEATER WALL SWITCH AND WALL THERMOSTAT WIRING OPTIONS HEATER WALL SWITCH WIRING FOR 120/240 VOLT NOTE: Before installing the unit complete the following: 1. Install main power connection with appropriate voltage as per Section C or Section D. 2. Install a 2 conductor wire with ground (3 wires total) from the heater switch wall box to the junction box on the unit. NOTE: Use a heater wall switch (on/off) that is rated for a minimum of 15 amps. 120 / 240 V
ملخص المحتوى في الصفحة رقم 16
HEATER WALL SWITCH WIRING DIAGRAM FOR 120/240 VOLT (SEE SECTION C OR SECTION D FOR MAIN POWER CONNECTION) RED – 2 WALL RED – 1 SWITCH GROUND - G 14 FIREPLACE JUNCTION BOX
ملخص المحتوى في الصفحة رقم 17
WALL MOUNTED THERMOSTAT WIRING FOR 120/240 VOLT NOTE: Before installing the unit complete the following: 1. Install main power connection with appropriate voltage as per Section C or Section D. 2. Install a 2 conductor wire with ground (3 wires total) from the thermostat wall box to the junction box on the unit. NOTE: Wiring of the thermostat must be completed prior to installing the unit. NOTE: The following installation instructions are for a single pole thermostat. 12
ملخص المحتوى في الصفحة رقم 18
WALL MOUNTED THERMOSTAT WIRING DIAGRAM FOR 120/240 VOLT (SEE SECTION C OR SECTION D FOR MAIN POWER CONNECTION) CONNECT GROUND TO WALL BOX RED – 2 WALL RED – 1 THERMOSTAT GROUND - G 16 FIREPLACE JUNCTION BOX
ملخص المحتوى في الصفحة رقم 19
FLAME OVERRIDE SWITCH WIRING FOR 120/240 VOLT NOT AVAILABLE WITH NO HEAT INSTALLATION NOTE: The fireplace can be wired to have a wall switch operate the heater independent of the flame. NOTE: Before installing the unit complete the following: 1. Install main power connection with appropriate voltage as per Section C or Section D. 2. Install a 2 conductor wire with ground (3 wires total) from the flame override switch wall box to the junction box on the unit. NOTE: Use a w
ملخص المحتوى في الصفحة رقم 20
FLAME OVERRIDE WALL SWITCH WIRING DIAGRAM FOR 120/240 VOLT (SEE SECTION C OR SECTION D FOR MAIN POWER C0NNECTION) NOT AVAILABLE WITH NO HEAT INSTALLATION BLUE – 4 WALL BLUE – 3 SWITCH GROUND - G 18 FIREPLACE JUNCTION BOX