ملخص المحتوى في الصفحة رقم 1
CHAMPION® SERIES
SINGLE PACKAGE HEAT PUMPS
Supersedes: 66297-YIM-B-1004 66297-YIM-C-0205
INSTALLATION INSTRUCTION
MODELS B1HH018 THRU 060
1.5 THRU 5 TON
(12 SEER)
GENERAL REFERENCE
YORK Model B1HH units are factory assembled heat pumps
Additional information on the design, installation, operation
designed for outdoor installation on a roof top or a slab. Field-
and service of this equipment is available in the following refer-
installed electric heater accessories are available to provide
en
ملخص المحتوى في الصفحة رقم 2
66297-YIM-C-0205 PRODUCT NOMENCLATURE B 1 H H 0 2 4 A 0 6 PRODUCT CATEGORY VOLTAGE CODE B = Single Package Heat Pumps 06 = 208/230-1-60 (Air Cooled) 25 = 208/230-3-60 46 = 460-3-60 PRODUCT GENERATION 58 = 575-3-60 1 = NEW or Current Design NOMINAL COOLING FACTORY CAPACITY (MBH) INSTALLED ELECTRIC HEAT PRODUCT IDENTIFIER 018 = 18,000 BTUH 042 = 42,000 BTUH 024 = 24,000 BTUH 048 = 48,000 BTUH A = No Electric Heat Installed HH = Heat Pump (12 SEER) 030 = 30,000 BTUH 060 = 60,000 BTUH 036 = 36,
ملخص المحتوى في الصفحة رقم 3
66297-YIM-C-0205 CLEARANCES CONDENSATE DRAIN All units require certain clearances for proper operation and A condensate trap is required to be installed in the conden- service. Refer to Figure 3 for the clearances required for com- sate drain. The plumbing must conform to local codes. Use a bustion, construction, servicing and proper unit operation. sealing compound on male pipe threads. Install the conden- sate drain line ( " NPTF) to spill into an open drain. WARNING:Do not permit overhang
ملخص المحتوى في الصفحة رقم 4
66297-YIM-C-0205 CONTROL WIRING THERMOSTAT UNIT TERMINAL STRIP NOTE: ** = Minimum wire size of 18 AWG ** HEAT ANTICIPATOR wire should be used for all field SHOULD BE SET AT 0.25 installed 24 volt wire. AMPS FOR ALL MODELS. 24 VOLT TRANSFORMER * PROGRAMMABLE THERMOSTAT ONLY * = Only required on units with supplemental electric heat. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verif
ملخص المحتوى في الصفحة رقم 5
66297-YIM-C-0205 TABLE 4 - ELECTRICAL DATA (BASIC UNIT) VOLTAGE SUPPLY MAX. MAX. OUTDOOR LIMITATIONS COMPRESSOR AIR MINIMUM FUSE HACR UNIT MODEL POWER SUP- FAN TRANSFORMER 1 BLOWER CIRCUIT SIZE, BREAKER POWER BHH PLY MOTOR, SIZE (VA) MOTOR, AMPACITY AMPS SIZE, FACTOR FLA MIN. MAX. RLA LRA FLA 2 AMPS 018 208/230-1-60 187 253 7.1 48.0 1.1 2.6 12.5 15 15 0.96 40 024 208/230-1-60 187 253 9.3 57.0 1.1 2.6 15.3 20 20 0.96 40 208/230-1-60 187 253 15.0 72.5 1.1 2.6 22.5 30 30 0.96 40 030 208/230-3-60 18
ملخص المحتوى في الصفحة رقم 6
66297-YIM-C-0205 TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) COMPRESSOR ELECTRIC HEAT ACCESSORY SUPPLY COND. MAX. MAX. AIR MINIMUM 2 POWER FAN FUSE HACR BLOWER CIRCUIT 1 TOTAL SUPPLY MOTOR SIZE, BREAKER RLA LRA MODEL NO. KW MOTOR, AMPACITY AMPS FLA AMPS SIZE FLA 2NH04500506 3.8 / 5.0 * 18.1 / 20.8 35.1 / 38.6 40 / 40 40 / 40 018 208/230-1-60 7.1 48.0 1.1 2.6 2NH04500706 5.6 / 7.5 * 27.1 / 31.3 46.4 / 51.6 50 / 60 50 / 60 2NH04500506 3.8 / 5.0 * 18.1 / 20.8 37.9 / 41.4 40 / 4
ملخص المحتوى في الصفحة رقم 7
66297-YIM-C-0205 TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued) COMPRESSOR ELECTRIC HEAT ACCESSORY SUPPLY COND. MAX. MAX. AIR MINIMUM 2 POWER FAN FUSE HACR BLOWER CIRCUIT 1 MODEL TOTAL SUPPLY MOTOR SIZE, BREAKER RLA LRA KW MOTOR, AMPACITY NO. AMPS FLA AMPS SIZE FLA 2NH04501058 10.0*** 9.6 19.8 20 20 036 575-3-60 4.7 32.0 0.4 1.5 2NH04501558 15.0*** 14.4 25.8 30 20 2NH04501058 10.0*** 9.6 20.7 25 25 042 575-3-60 5.4 34.0 0.4 1.5 2NH04501558 15.0*** 14.4 26.7 30 30 2NH04
ملخص المحتوى في الصفحة رقم 8
66297-YIM-C-0205 TABLE 6 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 600 CFM (B1HH018) OUTDOOR INDOOR WB TEMPERATURE, °F TEMPERATURE, 55 57 59 61 63 65 67 69 71 73 75 °F 65 5.5 5.8 6.1 6.4 6.7 7.0 7.3 13.0 18.7 24.5 30.2 70 — 5.1 5.5 5.9 6.3 6.7 7.1 12.4 17.8 23.1 28.5 75 — — — 5.4 5.8 6.3 6.8 11.8 16.8 21.8 26.8 80 ———— 5.4 6.0 6.6 11.2 15.8 20.5 25.1 85 ————— 5.6 6.3 10.6 14.9 19.1 23.4 90 ————— 5.3 6.1 10.0 13.9 17.8 21.7 95 —————— 5.8 9.4 12.9 16.5 20.0 100 ——————— 7.9 11.0 14.1 17.
ملخص المحتوى في الصفحة رقم 9
66297-YIM-C-0205 TABLE 10 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,000 CFM (B1HH030) OUTDOOR INDOOR WB TEMPERATURE, °F TEMPERATURE, 55 57 59 61 63 65 67 69 71 73 75 °F 65 — 5.8 10.8 15.8 20.8 25.8 30.8 31.7 32.6 33.4 34.3 70 — 5.1 9.3 13.6 17.8 22.1 26.3 28.0 29.6 31.3 32.9 75 — — 7.9 11.4 14.8 18.3 21.8 24.2 26.7 29.1 31.6 80 — — 6.4 9.1 11.9 14.6 17.3 20.5 23.7 27.0 30.2 85 — — — 6.9 8.9 10.8 12.8 16.8 20.8 24.8 28.8 90 ———— 5.9 7.1 8.3 13.1 17.9 22.6 27.4 95 ——————— 9.4 14.9 20.
ملخص المحتوى في الصفحة رقم 10
66297-YIM-C-0205 TABLE 14 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 1,400 CFM (B1HH042) OUTDOOR INDOOR WB TEMPERATURE, °F TEMPERATURE, 55 57 59 61 63 65 67 69 71 73 75 °F 65 19.6 22.0 24.4 26.8 29.2 31.6 34.0 34.8 35.6 36.4 37.2 70 19.1 21.5 23.9 26.2 28.6 31.0 33.3 34.2 35.0 35.9 36.7 75 18.7 21.0 23.4 25.7 28.0 30.3 32.7 33.6 34.5 35.4 36.2 80 18.2 20.5 22.8 25.1 27.4 29.7 32.0 32.9 33.9 34.8 35.8 85 17.8 20.0 22.3 24.6 26.8 29.1 31.3 32.3 33.3 34.3 35.3 90 15.5 17.5 19.5 21.5 23.5
ملخص المحتوى في الصفحة رقم 11
66297-YIM-C-0205 TABLE 18 - COOLING SUPERHEAT AT COMPRESSOR SUCTION, AIRFLOW = 2,000 CFM (B1HH060) OUTDOOR INDOOR WB TEMPERATURE, °F TEMPERATURE, 55 57 59 61 63 65 67 69 71 73 75 °F 65 — — — 5.4 6.8 8.3 9.8 15.5 21.2 27.0 32.7 70 ———— 6.3 7.8 9.2 14.9 20.6 26.2 31.9 75 ———— 5.8 7.2 8.6 14.2 19.9 25.5 31.1 80 ———— 5.3 6.7 8.0 13.6 19.2 24.8 30.3 85 ————— 6.1 7.4 12.9 18.5 24.0 29.6 90 —————— 5.8 10.5 15.3 20.0 24.8 95 ——————— 8.2 12.1 16.1 20.0 100 ——————— 6.8 10.0 13.1 16.3 105 ——————— 5.5 7.8 1
ملخص المحتوى في الصفحة رقم 12
66297-YIM-C-0205 TABLE 20 - SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE 230/460/575 volts EXTERNAL STATIC PRESSURE - IWG 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 MODEL NO. MOTOR BHH SPEED HI — — — — — — — — — — 668 401 652 386 — — — — — — 018 MED — — — — — — – — 654 233 541 209 — — — — — — — — LOW — — — — 702 220 641 206 536 183 — — — — — — — — — — HI — — — — — — — — — — — — — — 987 507 873 493 760 480 024 MED — — — — — — — — 935 338 867 322 800 304 733 286 867 268 — — LOW 900 290 850
ملخص المحتوى في الصفحة رقم 13
66297-YIM-C-0205 TABLE 21 - ADDITIONAL STATIC PRESSURE RESISTANCE RESISTANCE, IWG DESCRIPTION CFM 500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000 Wet Indoor coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07 Economizer 0.00 0.00 0.00 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08 Filter/Frame Kit 0.01 0.02 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03 0.04 0.05 0.05 0.06 0.06 0.07 Electric Heat 0.02 0.03 0.03 0.0
ملخص المحتوى في الصفحة رقم 14
66297-YIM-C-0205 HIGH VOLTAGE CONN. FRONT COMPRESSOR " DIA. KNOCKOUT SERVICE ACCESS HIGH VOLTAGE CONN. COMPARTMENT PANEL " DIA. KNOCKOUT DIMENSION LOW VOLTAGE CONN. “A” UNIT SIZE “ DIA. KNOCKOUT “A” (OVERALL) 018 - 036 33-1/2 042 - 060 41-1/2 SIDE SUPPLY AIR OPENING REFRIGERANT SIDE RETURN CONNECTIONS AIR OPENING ELECTRICAL/FILTER SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN. " DIA. KNOCKOUT (OVERALL) (OVERALL)
ملخص المحتوى في الصفحة رقم 15
66297-YIM-C-0205 SEQUENCE OF OPERATION will open and de-energize the indoor blower motor after the Anti-short Cycle Timer appropriate time delay. This unit has an anti-short cycle timer built in to the defrost con- trol. This timer will not permit the compressor to start within five Defrost Operation minutes after the completion of the last cycle or power interrup- The minimum time between defrosts can be field selected at tion. To bypass the anti-short cycle feature, short the “TEST” 30, 60 or
ملخص المحتوى في الصفحة رقم 16
66297-YIM-C-0205 gized. Power is supplied to the compressor and outdoor fan motor. The reversing valve remains in the heating position. motor, and the reversing valve switched to the cooling posi- When the fan switch on the thermostat is in the “AUTO” po- tion. When the fan switch on the thermostat is in the “AUTO” sition, the indoor blower is energized at the heating airflow. position the indoor blower motor is energized at the cooling 3. For units equipped with supplementary electric heat, whe
ملخص المحتوى في الصفحة رقم 17
66297-YIM-C-0205 TABLE 23 - THERMOSTAT SIGNALS (THREE PHASE UNITS) SIGNAL STATE BOARD FUNCTION ON FAN INSTANT ON “G” OFF FAN INSTANT OFF FAN INSTANT ON COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY) ON REVERSING VALVE ENERGIZED “G” & “Y” & “O” SYSTEM OPERATES IN COOLING COMPRESSOR AND OUTDOOR FAN INSTANT OFF OFF FAN 60 SEC. DELAY OFF FAN INSTANT ON ON COMPRESSOR AND OUTDOOR FAN INSTANT ON (AFTER ANTI-SHORT CYCLE DELAY) SYSTEM OPERATES IN HEATING “G” & “Y” COMPRESSOR AND OUT
ملخص المحتوى في الصفحة رقم 18
66297-YIM-C-0205 TROUBLESHOOTING CAUTION: The wire number or color and terminal designa- WARNING:Troubleshooting of components necessarily re- quires opening the electrical control box with the tions referred to may vary. Check the wiring label inside the control box access panel for the correct power connected to the unit. Use extreme care wiring. when working with live circuit! Check the unit nameplate for the correct range before making any CAUTION: If the variable speed motor found in the BH
ملخص المحتوى في الصفحة رقم 19
66297-YIM-C-0205 TYPICAL WIRING DIAGRAM LEGEND (See page 18) $ % ’ &