ملخص المحتوى في الصفحة رقم 1
s
Program Library Karlsruhe
S79220-A0977-A-10-7637
Product Information
AS 488/TM
Var. M02.02 Issue: November, 2001
Descriptors
TELEPERM M , AS 488/TM , Software variant M , UPGRADE , UPDATE
Summary
The present Product Information relates to the System Software Package:
Name Variant Issue Product no. (MLFB)
AS 488/TM M 02.02 6DS2 410-0XX00-0XA0
6DS2 410-0XX00-0XB0
AS 488/TM M 02.02 6DS2 410-0XX00-0XC2
upgrade / update 01.08
Description:
ملخص المحتوى في الصفحة رقم 2
Product Information November, 2001 AS 488/TM M02.02 1 Scope The product information for the system software M02.01/M01.07 remains valid. The following information represents a supplement. The delivery consists of: 6DS2 410-0XX00-0XA0 6DS2 410-0XX00-0XC2 6DS2 410-0XX00-0XB0 (Upgrade / Update) AS 488/TM Memory Card Diskette 3,5" with AS 488/TM software Diskette 3,5" with tools for Diskette 3,5" with tools for installation installation Software contract and Software contract r
ملخص المحتوى في الصفحة رقم 3
Product Information November, 2001 AS 488/TM M02.02 1.1 Supplementary Documentation In addition to the tools required for startup of your AS 488/TM, the commissioning diskette contains a document file for the service terminal (within the directory ASBEDIEN or ASBEDIEN.NT): ASBEDI_E.doc User description for the Commissioning Terminal (IBS terminal) For further information by seperate ordering to C79000-G8076-C700 please ask your Siemens sales partner for a document diskette. This in
ملخص المحتوى في الصفحة رقم 4
Product Information November, 2001 AS 488/TM M02.02 1.2 AS System File for PROGRAF AS+ Your commisioning diskette contains a directory PROGRAF after extracting. This contains the system file AS.SYS required for PROGRAF AS+. Copy the file AS.SYS into your PROGRAF PC into the directory drv:\PROGRAF\USER\ The system file of the AS 488/TM automation system is then known to PROGRAF AS+. Carry out your PROGRAF AS configuring in the usual manner. Note: From PROGRAF AS+ V3.00 onwards,
ملخص المحتوى في الصفحة رقم 5
Product Information November, 2001 AS 488/TM M02.02 2 Commissioning The Memory Card contains the entire system software for AS 488/TM. It responds with the version ID M02.02 . To perform an upgrade or update from diskette, an AS 488/TM memory card must be available. The upgrade procedure is performed offline with a PC or a programming device having a compatible MC interface (e.g. PG740). The update procedure is performed either from the IBS terminal (online) or from a programmin
ملخص المحتوى في الصفحة رقم 6
Product Information November, 2001 AS 488/TM M02.02 2.1 Startup by Commissioning Terminal The extracted IBS tool diskette contains your local tool in the directory ASBEDIEN. Install this on your PC to be used for commissioning of the AS 488/TM according to the installation instructions in the document file ASBEDI_E.DOC in the directory ASBEDIEN, and connect your PC to the serial commissioning interface of your AS 488/TM via a serial interface. For operation under Windows 3.1, a PI
ملخص المحتوى في الصفحة رقم 7
Product Information November, 2001 AS 488/TM M02.02 2.2 Procedure for Upgrade to M02.02 with Programming Device PG740 Stop your AS running (e.g. with STO) and then switch the AS off before pulling the memory card! For the upgrade, insert the memory card into the MEM-CARD slot of the PG740. Now start the batch UPGRADE.BAT (if applicable, information on the memory card drive, default setting is E:) resp. the corresponding link. Syntax: UPGRADE or UPGRADE E: This batch file - cr
ملخص المحتوى في الصفحة رقم 8
Product Information November, 2001 AS 488/TM M02.02 2.2.1 Restoring a Memory Card This restore is necessary if the memory card is no longer bootable on an AS 488/TM (if it has been deleted with the SIMATIC Manager for example). The procedure corresponds to an upgrade (see chapter 2.2). Special features: • Attempting to copy the old files from the memory card to the programming device, with a faulty (empty) memory card appears the error message: Not ready when reading from drive E:
ملخص المحتوى في الصفحة رقم 9
Product Information November, 2001 AS 488/TM M02.02 2.3 Procedure for Update M01.07 (resp. M01.06/05/04) to M01.08 2.3.1 Update by Commissioning Terminal You will find the files needed for an update on the UPGRADE/UPDATE diskette too. Please copy all files from the directory C:\UPGRADE\AS_SW.202 (without sub-directory M02.02) and from the directory C:\UPGRADE\UPDATE_M.108 to the directory ‘C:\ASBEDIEN’ on your Commissioning Terminal PC or into the current working directory (e.g. C:\
ملخص المحتوى في الصفحة رقم 10
Product Information November, 2001 AS 488/TM M02.02 To check the update procedure, start the new ASBEDIEN and select the AS status screen ( BT,STAT:@; ). In addition to the start-up message, the system version ( M01.08 ) is displayed. Note: If there is already a version M02.01 on the memory card, you can use the files from directory C:\UPGRADE\AS_SW.202\M02.02 instead of the files from C:\UPGRADE\Update_M.108 for the online update (additionally to the files from C:\UPGRADE\AS_SW.2
ملخص المحتوى في الصفحة رقم 11
Product Information November, 2001 AS 488/TM M02.02 2.4 Installation of the Reloadable DP Driver Blocks (DPAE, DPAA, DPBE, DPBA) In addition to the execution system and the standard blocks of the AS 488/TM, your memory card contains a so-called reloadable file with the optimized driver blocks for the PROFIBUS-DP I/O bus. These blocks are not present in the system data area of the AS, and are thus not activated automatically. You can load these blocks into your user memory and activat
ملخص المحتوى في الصفحة رقم 12
Product Information November, 2001 AS 488/TM M02.02 2.5 Installation of the Reloadable IP262 Driver Blocks (RIP, KRIP) In addition to the execution system and the standard blocks of the AS 488/TM, your memory card contains a so-called reloadable file with the optimized driver blocks for the controller module IP262. These blocks are not present in the system data area of the AS, and are thus not activated automatically. You can load these blocks into your user memory and activate them
ملخص المحتوى في الصفحة رقم 13
Product Information November, 2001 AS 488/TM M02.02 3 Removed Errors F: Function concerned A: Appearance M: Modification • F: ASBEDIEN: command LANW A: The transmission doesn't work. Afterwards also the other commands don't work (COPY_PC, COPY_TM, DIR_TM). M: Operating task corrected within the AS system software. • F: S5KS/S5KE A: When utilizing the maximum permissible message frame length of 128 bytes with TELEPERM I/O modules, the telegram is rejected (shorter and longe
ملخص المحتوى في الصفحة رقم 14
Product Information November, 2001 AS 488/TM M02.02 4 Extended Functions 4.1 General Extensions F: Function concerned A: Appearance E: Extension • F: Central configuration via bus A: If the disconnection is not finished correctly, the AS continues transmitting picture data (S 38x is appearing as error message). If another AS is selected from the configuration AS via ANMS, pictures were shown from the last linked AS and the new linked AS alternately. E: Now unfamiliar AS pi
ملخص المحتوى في الصفحة رقم 15
Product Information November, 2001 AS 488/TM M02.02 4.3 Online Configuring as Stand-alone Operating Terminal As replacement for an AS 230/235 local operating console with screen, configuration and process operating keyboard, the Online Configuring Console of PROGRAF AS+/NT has been extended for AS 488/TM with the following functions: ♦ colored picture transmission ♦ PBT (process operating console) function keys (analogous to ASBEDIEN) The programm for the bus operating console is
ملخص المحتوى في الصفحة رقم 16
Product Information November, 2001 AS 488/TM M02.02 5 Extended Documentation 5.1 Restart of AS 488/TM with Interface Module TPM 478 With each restart of the AS 488/TM the interface module TPM 478 will be parameterized new. This happens with: - Power on - Boot by MRES key switch - RSOF (by operation or key switch) - Loading (LA,name; or LA:name;) - Loading via bus (LAB or LABR) - LOES. During this parameterization the SYST.WART configuration is passed to the TPM 478 module,
ملخص المحتوى في الصفحة رقم 17
Product Information November, 2001 AS 488/TM M02.02 6 Limited Operating Performance No safety-relevant software faults are currently known; the known faults are assigned to fault class 3 and lower. Caution: When working on initialization files (*.INI), tabs (09H) should not be used. Spaces (20H) should be used instead. Failure to comply could lead to interpretation errors. AS 488/TM with TELEPERM M I/Os: The limitations with respect to use of TM I/Os (module types), all
ملخص المحتوى في الصفحة رقم 18
Product Information November, 2001 AS 488/TM M02.02 Further information: The arithmetic accuracy of the AS 488/TM with floating-point numbers is higher than that of the AS 235. There may therefore be small deviations in the last digits of the mantissa in the case of calculated analog values or floating-point constants in TML. The CD coupling is not implemented in the AS 488/TM. Any attempt to register a CD coupling from OS or AS 235 will be rejected. Remedy: When importing struc