ملخص المحتوى في الصفحة رقم 1
website http://www.lgservice.com
LG
LG
Room Air Conditioner
SERVICE MANUAL
MODELS: LAN121CNM (ASNC121ERH0)
LAU121CNM (ASUC121EUH0)
LA121HPMI (ASNH121ERH0)
LA121HPMO (ASUH121EUH0)
LAN121HNM (ASNH121ERH0)
LAU121HNM (ASUH121EUH0)
LA121CPMI (ASNC121ERH0)
LA121CPMO (ASUC121EUH0)
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY
PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
ملخص المحتوى في الصفحة رقم 2
Air Conditioner Service Manual TABLE OF CONTENTS Safety Precautions..........................................................................................................................................3 Dimensions......................................................................................................................................................9 Symbols Used in this Manual........................................................................................................
ملخص المحتوى في الصفحة رقم 3
Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. This symbol indicates the possibility of death or serious injury. This symbol indicates the possibility of injury or damage to properties only. Meanings of symbols used in this manual are as shown below. Be su
ملخص المحتوى في الصفحة رقم 4
Safety Precautions Be cautious when unpacking For installation, always contact Do not install the product on a and installing the product. the dealer or an Authorized defective installation stand. Service Center. • Shape edges could cause injury. • There is risk of fire, electric • It may cause injury, accident, or Be especially careful of the sharp shock, explosion, or injury. damage to the product. edges. Be sure the installation area Install the indoor unit on the Do not handle the pipe by
ملخص المحتوى في الصفحة رقم 5
Safety Precautions Do not place a heater or other Do not let the air conditioner run Do not store of use flammable appliances near the power for a long time when the humidi- gas or combustibles near the air cable. ty is very high and a door or a conditioner. window is left open. • There is risk of fire, failure of the • Moisture may condense and wet • There is risk of fire or product fail- product, and/or electric shock. or damage furnishings. ure. Do not use the product in a When flammable g
ملخص المحتوى في الصفحة رقم 6
Safety Precautions Ventilate the product from time Unplug the appliance before When the product is not be used to time when operating it togeth- performing cleaning or mainte- for a long time disconnect the er with a stove, etc. nance. power supply plug or turn off the breaker. • There is risk of fire or electrical • There is risk of electric shock. • There is risk of product damage shock. or failure, or unintended opera- tion. Take care to ensure that nobody could step on or Do not insert ha
ملخص المحتوى في الصفحة رقم 7
Safety Precautions Do not install the product where Use two or more people to lift Do not install the product where the noise or hot air from the out- and transport the air conditioner it will be exposed to sea wind door unit could damage the (salt spray) directly. neighborhoods. • It may cause a problem for your • Avoid personal injury. • It may cause corrosion in the neighbors. product. Corrosion, particularly on the condenser and evaporator fins, could cause product mal- function or ineffic
ملخص المحتوى في الصفحة رقم 8
Dimensions Always insert the filter securely. Clean the filter Do not drink the water drained from the unit. every two weeks or more often if necessary. • A dirty filter reduces the efficiency of the air condi- • It is not sanitary and could cause serious health tioner and issues. Use a firm stool or ladder when cleaning or main- Replace all the batteries in the remote. taining the air conditioner. • Be careful and avoid personal injury. • There is risk of fire or explosion. Disuse Do not rec
ملخص المحتوى في الصفحة رقم 9
Dimensions Dimensions Symbols Used in this Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that could cause harm to the air conditioner. This symbol indicates special notes. NOTICE Indoor Unit H D W Installation plate Model 12k Btu Series Dimension W mm 915(36.0) H mm 282(11.1) D mm 165(6.5) Service Manual 9
ملخص المحتوى في الصفحة رقم 10
Dimensions Outdoor Unit 1. 12k L2 W L3 Gas side (3-way valve) Liquid side (2-way valve) MODEL 12k DIM unit W mm(inch) 770(30.3) H mm(inch) 540(21.3) D mm(inch) 245(9.6) L1 mm(inch) 287(11.3) L2 mm(inch) 64(2.5) L3 mm(inch) 518(20.4) L4 mm(inch) 10(0.4) L5 mm(inch) 100(3.9) 10 Room Air Conditioner H L1 D L4 L5
ملخص المحتوى في الصفحة رقم 11
Introduction Introduction Symbols Used In This Manual This symbol alerts you to the risk of electric shock. This symbol alerts you to hazards that may cause harm to the air condi- tioner. NOTICE This symbol indicates special notes. Features Air Inlet Air Filter Front Panel Signal Receptor Air Intake Vents Connecting Wires Connecting Wires Air Intake Vents Piping Piping Air Outlet Drain Hose Vents Drain Hose Air Outlet Vents Base Plate Base Plate Service Manual 11
ملخص المحتوى في الصفحة رقم 12
Installation Installation Read carefully, and then follow step by step. Installation Parts Installation plate Type "A" screw and plastic anchor Remote Control Holder Type "B" screw Installation Tools Figure Name Figure Name Screw driver Ohmmeter Electric Drill Hexagonal wrench Measuring Tape, Knife Ammeter Hole Core Drill Gas Leak Detector Thermometer, Spanner Level Torque wrench Flaring Tool Set 12 Room Air Conditioner
ملخص المحتوى في الصفحة رقم 13
Installation Installation Map NOTICE Installation parts you should purchase. Installation plate Sleeve Bushing-Sleeve Putty(Gum Type Sealer) Bend the pipe as closely on the wall as possible, but be careful that it doesn't break. Air Discarge Vertical Air deflector Operation Indication Lamps/ Vinyl tape (Wide) Signal Receptor • Apply after carrying out a drainage test. Forced Operation Button • To carry out the drainage test, remove the air filters Saddle and pour water into the heat
ملخص المحتوى في الصفحة رقم 14
Installation Confirm The Refrigerant 1. Check the quality label on the indoor and outdoor unit. 2. Make certain that the refrigerant is R-410A. NOTICE THIS PRODUCT CONTAINS R-410A REFRIGERANT 1) Different compressor oil - R-410A(Polyol ester) / R-22(Mineral). - Do not mix the existing mineral oil. - Do not apply used pipe, tools and gauges covered with the existing mineral oil. 2) Absorption of moisture -Compressor’s oil has the high absorption rate of moisture. 3) Composition - R-410A(R32:R125=
ملخص المحتوى في الصفحة رقم 15
Installation Select the Best Location 6. Use a stud finder to locate studs to prevent Indoor unit unnecessary damage to the wall. 1. Do not have any heat or steam near the unit. 2. Select a place where there are no obstacles in front of the unit. More than 3. Make sure that condensation drainage can be 20cm(7.9in) More than conveniently routed away. 30cm(11.8in) 4. Do not install near a doorway. More than 30cm(11.8in) 5. Ensure that the space around the left and right More than 1.5m(4.9ft) of
ملخص المحتوى في الصفحة رقم 16
Installation Piping Length and Elevation Standard Max. Max. Additional Pipe Size Capacity Length Elevation length Refrigerant (Btu/h) Suction Evap m(ft) B m(ft) A m(ft) g/m(oz/ft) 12k Ø12.7(1/2") Ø6.35(1/4") 7.5(25) 7.5(25) 15(49) 20(0.22) Outdoor unit Indoor unit Outdoor unit A Oil trap A Indoor unit B Outdoor unit Indoor unit B B In case more than 5m(16.4ft) • Capacity is based on standard length and maximum allowance length is on the basis of reliability. • Oil trap should be installed every
ملخص المحتوى في الصفحة رقم 17
Installation How to Mount Installation Plate The wall you select should be strong and solid enough Installation Plate to prevent vibration 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. Chassis • Mount the installation plate horizontally by aligning the Hook centerline using a level. Type “A” 2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the instal- lation
ملخص المحتوى في الصفحة رقم 18
Installation Flaring Work Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the follow- ing procedure. Cut the pipes and the cable. 1. Use the piping kit accessory or the pipes purchased locally. Copper 2. Measure the distance between the indoor and the out- Slanted Uneven Rough pipe 90° door unit. 3. Cut the pipes a little longer than measured distance. 4. Cut the cable 1.5m(59.1in) longer than the pipe length. Burrs removal Pipe 1. Completely rem
ملخص المحتوى في الصفحة رقم 19
Installation Connecting The Piping Indoor 1. Prepare the indoor unit's piping and drain hose for installation through the wall. 2. Remove the plastic tubing retainer(see the illus- tration by) and pull the tubing and drain hose away from chassis. 3. Replace only the plastic tubing holder 1, not the holder 2 in the original position. For left rear piping Route the indoor tubing and the drain 1 2 hose in the direction of rear left. Connecting cable Insert the connecting cable into the indoor unit
ملخص المحتوى في الصفحة رقم 20
Installation Connecting the pipings to the indoor unit Wrap the insulation material around the and drain hose to drain pipe. connecting portion. • Put a couple drops of refrigerant oil on the face • Overlap the connection pipe insulation material of the flare before assembling taking care not to and the indoor unit pipe insulation material. Bind add any contaminants. them together with vinyl tape so that there is no • Align the center of the pipings and sufficiently gap. Plastic bands Insulation