ملخص المحتوى في الصفحة رقم 1
GE
™
Entellisys Low Voltage Switchgear
System Administrator Manual
ملخص المحتوى في الصفحة رقم 2
DEH-230 Warnings, Cautions, and Notes as used in this publication Warnings WARNING! Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that could cause personal injury exist in this equipment or may be associated with its use. Warning notices are also used for situations in which inattention or lack of equipment knowledge could cause either personal injury or damage to equipment. Cautions CAUTION: Caution notices are used for situa
ملخص المحتوى في الصفحة رقم 3
How to contact us Please have your Entellisys System Summary # and Sub # ready when calling. This information can be found on the Entellisys HMI on the System Health screen by clicking the Job Info button. Post Sales Service GE Switchgear 510 Agency Road West Burlington, IA 52655 Phone (toll free): 1-888-437-3765 Additional information: www.entellisys.com/support For Option Upgrades and CPU Replacement needs only, e-mail us at entellisys.lvs.pss@ge.com.
ملخص المحتوى في الصفحة رقم 4
ملخص المحتوى في الصفحة رقم 5
Contents 1 System administrator roles and responsibilities 1.1 Security Champion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.1.1 System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2 Pre-programming settings prior to switchgear arrival 3 Commissioni
ملخص المحتوى في الصفحة رقم 6
13 Other maintenance functions 13.1 Viewing and updating circuit breaker names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 13.2 Viewing and updating circuit breaker accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 13.3 Installing CPU firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ملخص المحتوى في الصفحة رقم 7
1 System administrator roles and 1 responsibilities The Entellisys™ Low Voltage Switchgear system requires a System Administrator for oversight of critical functions. Those critical functions are described in this guide. Chapter 1 provides an overview of the roles and responsibilities. The following chapters describe how to perform the functions, in detail. 1.1 Security Champion The most important role of the System Administrator is to control the access to the system. There are several for
ملخص المحتوى في الصفحة رقم 8
1 8 System administrator roles and responsibilities
ملخص المحتوى في الصفحة رقم 9
2 Pre-programming settings prior to switchgear arrival 2 Entellisys provides a method for users to work on the system settings before the switchgear arrives. Once the gear is installed and control power is applied, the saved settings can be written to the system. To pre-program Settings, the “Entellisys Remote HMI – User Interactive version” must be purchased. GE will ship the Remote HMI software, System Administrator Manual (this manual), and a System Archive when the switchgear ships fro
ملخص المحتوى في الصفحة رقم 10
2 2 10 Pre-programming settings prior to switchgear arrival
ملخص المحتوى في الصفحة رقم 11
3 Commissioning the switchgear Installing and starting up the switchgear is an important event for the System Administrator. The following steps must be followed when commissioning the switchgear. 3 � Step 1: Reset Passwords. See Passwords on page 13. � Step 2: Set User Settings. See DEH-231 Entellisys Low Voltage Switchgear System User Manual. � Step 3: Set Local HMI flags. See Local HMI on page 17. � Step 4: Set System Time Synchronization. See Time synchronization on page 19. � Step 5: Confi
ملخص المحتوى في الصفحة رقم 12
3 12 Commissioning the switchgear
ملخص المحتوى في الصفحة رقم 13
4 Passwords 4.1 HMI permissions and passwords The Entellisys HMI requires a login name and password. This login sets the permissible actions 4 for the session. Each user's permissions are programmable to provide flexibility. Only the Administrator can set permissions, login names, and passwords. CAUTION: Enabling Group Permissions for features that allow the changing of settings and/or access to control functions must be restricted to accounts for qualified personnel only. As a reminder, use
ملخص المحتوى في الصفحة رقم 14
Once Groups are established, individual Users can be created. Users can have individual login names and passwords. Passwords consist of 3-20 alphanumeric characters. Both login names and passwords are case-insensitive. NOTE: There are three predefined Groups that cannot be modified. Beneath those Groups are two Users that are fixed and cannot be modified. The passwords for all can be changed. The predefined groups and users are: 4 Group: Administrator User: Administrator Group: Operator Us
ملخص المحتوى في الصفحة رقم 15
To change a password 1. On the Main Menu, click the User Administration button. Only Administrators can access User Administration. For all others, the button will not appear on the Main Menu. 2. Select the desired user group on the left-side pane. Expand the group by clicking the + symbol and click a user name. 3. Enter the new password in the New Password field. 4. Confirm your password by re-entering the new password in the Confirm Password field. Click OK to save your new password (or cl
ملخص المحتوى في الصفحة رقم 16
® 4.2 Modbus security 4.2.1 Control and settings passwords The CPUs require extra passwords to change settings (i.e., Short Time pickup delay setting) and to send commands (i.e., Open Breaker command). These passwords apply to all clients that 4 access the Entellisys system through Modbus communications including the Entellisys HMI, SCADA, or Building Automation, etc. NOTE: The system ships with default CPU Modbus Settings and Command passwords. The System Administrator should change these p
ملخص المحتوى في الصفحة رقم 17
To change the Settings and/or Command passwords 1. On the Main Menu, click the Maintenance button. The button will only be displayed if access is allowed with the current login permissions. 2. Click the Modbus Security tab. The Modbus Security screen has options to change both CPU A and CPU B Command and Settings passwords. NOTE: It is recommended that the passwords in CPU A and CPU B be set to the same value. 4 3. Enter the new commands password in the New Password field. 4. Re-enter the pas
ملخص المحتوى في الصفحة رقم 18
Figure 4-6 Breaker Control screen 4 � The CPU reserves a communication port for the HMI with the Local HMI flag set. The CPUs can support up to 8 simultaneous communication ports for Modbus clients. Once the limit is exceeded, clients will be blocked until a port is free. The Local HMI flag has special ports reserved for its use to prevent other clients from locking it out. NOTE: All In-Gear and Near-Gear Touchscreen HMIs should have the “Local HMI” set. To set an HMI as a local HMI 1. On the
ملخص المحتوى في الصفحة رقم 19
5 Time synchronization In the Entellisys System, time is recorded when events occur for diagnostic purposes. Events are generated from both the HMI and the CPU components and the time stamps used are derived from time set in the component. One HMI in the system will be configured to synchronize time with the CPUs. Periodically, the HMI will synchronize time to ensure the time in the two CPUs is consistent. Time synchronization configuration is done by GE during the system start up. 5 NOTE: T
ملخص المحتوى في الصفحة رقم 20
5 20 Time synchronization