CMC AC Variable Speed Drive
Series S
1 1 - 1 1 -- - 30 30 H 30 H 30 H HP P P P (230/4 (230/4 (230/4 (230/460 6 6 60V) 0V) 0V) V)
Installation, Operation and
Maintenance Instruction
Read this manual carefully before installing, wiring,
operating, servicing or inspecting the drive.
Keep this manual within easy reach for quick reference.
ملخص المحتوى في الصفحة رقم 2
Thank you for purchasing CMC Variable Frequency Drives ! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are classified as follows: Improper operation may result in serious personal injury or death. WARNING Improper operation may result in slight to medium personal injury or property damage. CAUTION Throughout this manual we use the following two illustrations to make
ملخص المحتوى في الصفحة رقم 3
Operate the switches with dry hands. Otherwise, you may get an electric shock. Do not use the cable when its insulating tube is damaged. Otherwise, you may get an electric shock. Do not subject the cables to scratches, excessive stress, heavy loads or pinching. Otherwise, you may get an electric shock. CAUTION Install the inverter on a non-flammable surface. Do not place flammable material nearby. Otherwise, fire could occur. Disconnect the input power if the i
ملخص المحتوى في الصفحة رقم 4
Use the inverter under the following environmental conditions: Ambient - 10 ~ 40 ℃ (non-freezing) temperature Relative 90% RH or less (non-condensing) humidity - 20 ~ 65 ℃ Storage temperature Location Protected from corrosive gas, combustible gas, oil mist or dust 2 Altitude, Max. 1,000m above sea level, Max. 5.9m/sec (0.6G) Vibration or less Atmospheric 70 ~ 106 kPa pressure (2) Wiring Do not connect a power factor correction capacitor, surge suppressor, or RFI
ملخص المحتوى في الصفحة رقم 5
Use an insulation-rectified motor or take measures to suppress the micro surge voltage when driving 400V class motor with inverter. A micro surge voltage attributable to wiring constant is generated at motor terminals, and may deteriorate insulation and damage motor. Before operating unit and prior to user programming, reset user parameters to default settings. Inverter can easily be set to high-speed operations, Verify capability of motor or machinery prior to operating unit. Stopping
ملخص المحتوى في الصفحة رقم 6
ملخص المحتوى في الصفحة رقم 7
CONTENTS USER SELECTION GUIDE (ACTIONMASTER SPECIFICATIONS) .....................................................................II CHAPTER 1 - INSTALLATION...................................................................................................................... 1-2 1.1 Inspection..........................................................................................................................................................1-2 1.2 Environmental Conditions ..........
ملخص المحتوى في الصفحة رقم 8
6.6 Application Group [APP]..................................................................................................................................6-2 CHAPTER 7 - OPTIONS ................................................................................................................................ 7-2 7.1 Sub-A board ......................................................................................................................................................7-2 7.2 Sub-B Boa
ملخص المحتوى في الصفحة رقم 9
USER SELECTION GUIDE (ACtionMaster SPECIFICATIONS) 230V Class (1 ~ 30HP) Model Number 008 015 022 037 055 075 110 150 185 220 SV xxx ACtionMaster - 2 Motor HP 1 2 3 5 7.5 10 15 20 25 30 1 Rating kW 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 2 Capacity [kVA] 1.9 3.0 4.5 6.1 9.1 12.2 17.5 22.9 28.2 33.5 Output FLA [A] 5 8 12 16 24 32 46 60 74 88 Ratings Frequency 0 ~ 400 Hz (0-120Hz for Vector control) 3 Voltage 200 ~ 230 V Input Voltage 3 Phase, 200 ~ 230 V (± 10 %) Ratings Freq
ملخص المحتوى في الصفحة رقم 10
Max. Continuous 5 5 seconds 5 seconds 15 seconds Controlled by Braking Unit Baking Time Max. Duty 3 % ED 2 % ED 5 % ED 5 % ED Weight [lbs] 10.4 10.4 10.6 10.8 17.0 17.0 30.6 31.7 44.1 44.1 460V Class (40 ~ 100HP) Model Number 300 370 450 550 750 SV xxx ACtionMaster - 4 40 50 60 75 100 Motor HP 1 Rating 30 37 45 55 75 kW 2 45 56 68 82 100 Capacity [kVA] 61 75 91 110 152 Output FLA [A] Ratings Frequency 0 ~ 400 Hz (0-120Hz for Vector control) 3 Voltage 380 ~ 460 V Input
ملخص المحتوى في الصفحة رقم 11
Jog Jog Operation Auto Operation Operates via Internal Sequence by Setting Multi-Function Terminal (5 Way * 8 Step) Fault Reset Trip Status is Removed when Protection Function is Activated Operating Status Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Under Voltage, Inverter Overheating, Running, Stop, Constant Speed, Inverter By-Pass, Speed Searching, Auto-Operation Step, Auto-Operation Sequence Fault Output Contact Output (30A, 30C, 30B) – AC 250V 1A, DC 30V 1A
ملخص المحتوى في الصفحة رقم 12
ملخص المحتوى في الصفحة رقم 13
CHAPTER 1 - INSTALLATION 1.1 Inspection Inspect the inverter for any damage that may have occurred during shipping. Check the nameplate on the inverter. Verify the inverter unit is the correct one for the application. The numbering system for the inverter is as shown below. SV 008 AC 2 N U CMC Inverter Motor Capacity Series Name Input Voltage 008: 1 HP 185: 25 HP 2 : 200 ~ 230V ( ± ± ± ±10%) 50/60Hz 015: 2 HP 220: 30 HP 4 : 380 ~ 4
ملخص المحتوى في الصفحة رقم 14
Chapter 1 - Installation 1.4 Other Precautions Do not carry the inverter by the front cover. Do not install the inverter in a location where excessive vibration is present. Be cautious when installing on presses or moving equipment. The life span of the inverter is greatly affected by the ambient temperature. Install in a location where temperature are within permissible limits (- 10 ~ 40 ℃). The inverter operates at high-temperatures - install on a non-combustible surfac
ملخص المحتوى في الصفحة رقم 15
Chapter 1 - Installation 1.5 Dimensions Frame # 1: 1 ~ 5 HP Frame # 2: 7.5 ~ 10 HP Frame HP Model Number W1 W2 H1 H2 D1 1 SV008ACtionMa ster-2/4 2 SV015ACtionMa ster-2/4 150 130 284 269 156.5 Frame # 1 3 SV022ACtionMa (5.91) (5.12) (11.18) (10.69) (6.16) ster-2/4 5 SV037ACtionMa ster-2/4 7.5 SV055ACtionMa ster-2/4 200 180 355 340 182.5 Frame # 2 (7.87) (7.09) (13.98) (13.39) (7.19) 10 SV075ACtionMa ster-2/4 1-3
ملخص المحتوى في الصفحة رقم 16
Chapter 1 - Installation BLANK 1-4
ملخص المحتوى في الصفحة رقم 17
Chapter 1 - Installation Frame # 3: 15 ~ 20 HP Frame # 4: 25 ~ 30 HP mm (inches) Frame HP Model Number W1 W2 H1 H2 D1 15 SV110ACtionMa ster-2/4 250 230 385 370 201 Frame # 3 20 SV150ACtionMa (9.84) (9.06) (15.16) (14.57) (7.91) ster-2/4 25 SV185ACtionMa ster-2/4 304 284 460 445 234 Frame # 4 30 SV220ACtionMa (11.97) (11.18) (18.11) (17.52) (9.21) ster-2/4 1-5
ملخص المحتوى في الصفحة رقم 18
Chapter 1 - Installation BLANK 1-6
ملخص المحتوى في الصفحة رقم 19
Chapter 1 - Installation 1.6 Basic Wiring Dynamic Braking Unit (Optional) 4 DB Unit(Optional) DB Resitor 3 DC Bus Choke (Optional) P N B1 B2 DC Bus Choke DB Resistor MCCB(OPTION) 1 1 1 P1 P2 N 3 φ R U MOTOR 230/460 V S V 50/60 Hz T W G ( ) + FM FM Output Frequency Meter Forward Run/Stop FX (0~10V Linear) Reverse Run/Stop RX 5G Inverter Disable BX Fault Reset RST Jog JOG Multi-function Input 1 P1 Factory Setting: Multi-function Input 2 P2 ‘Speed-L’ Multi-functi
ملخص المحتوى في الصفحة رقم 20
Chapter 1 - Installation 1.7 Power Terminals Type A Configuration: 1 ~ 5 HP (SV008ACtionMaster-2, SV015ACtionMaster-2, SV022ACtionMaster-2, SV037ACtionMaster-2, SV008ACtionMaster-4, SV015ACtionMaster-4, SV022ACtionMaster-4, SV037ACtionMaster-4) R S T G N B1 B2 U V W Type B Configuration: 7.5 ~ 10 HP (SV055ACtionMaster-2, SV075ACtionMaster-2, SV055ACtionMaster-4, SV075ACtionMaster-4) R S T G P N B1 B2 U V W Type C Configuration: 15 ~ 30 HP (SV110ACtionMaster-2, SV150ACt