ملخص المحتوى في الصفحة رقم 1
Operation
®
Symmetra PX UPS,
Power Distribution Unit, and
XR Battery Enclosure
160 kW 400 V
SY160K160H
PDUM160H-B
SYCFXR9
ملخص المحتوى في الصفحة رقم 2
ملخص المحتوى في الصفحة رقم 3
About this Manual ® This manual is for the 160 kW Symmetra PX UPS, Power Distribution Unit (PDU-XR), and XR Battery enclosure. It refers to important safety warnings and instructions, gives an introduction to the display interface, and provides information on operation and troubleshooting. Companion manuals For additional information, refer to the following Symmetra PX manuals: • Receiving and unpacking (990-3013) • Safety (990-2984) • Installation (990-3017) • Power module replacement (990-30
ملخص المحتوى في الصفحة رقم 4
ملخص المحتوى في الصفحة رقم 5
Contents Safety................................................................................1 Overview...........................................................................3 User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Interface area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Display interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Menu
ملخص المحتوى في الصفحة رقم 6
Maintenance................................................................... 15 Parts Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 How to determine if you need a replacement part . . . . . . . . . . . . . 15 How to return parts to APC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 How to remove a power module . . . . . . . . . .
ملخص المحتوى في الصفحة رقم 7
Safety Warning: All safety instructions in the Safety sheet (990-2984) should be read, understood, and followed prior to handling the system. Failure to do so could result in equipment damage, serious injury, or death. For safety reasons, only the following parts are replacable. If other components of the system require maintenance, contact APC Customer Support using the phone numbers on the back cover of this manual. • power distribution module • power modules • batteries • intelligence mod
ملخص المحتوى في الصفحة رقم 8
ملخص المحتوى في الصفحة رقم 9
Overview User Interface Interface area When green, power to the load is on. When flashing yellow, the load is LOAD POWERED LED supplied through the batteries or the unit is in bypass. CHECK LOG LED When green, a new event has been added to the event log. WARNING LED When yellow, there are one or more warning alarms in the system. CRITICAL LED When red, there are one or more critical alarms in the system. LCD SCREEN Displays alarms, status data, instructional help, and configuration item
ملخص المحتوى في الصفحة رقم 10
Overview: User Interface Display interface Overview screens. When the system is running, the display will scroll through screens showing information about the system, and any active alarms. Note: The data values shown are for example only. No Active Alarms System Date/Time: 28-Mar-2007 10:37:01 Volts Out Volts In L1: 230 L1: 230 L2: 230 L2: 230 L3: 230 L3: 230 Out Amps kW %kW L1: 162 37.3 70 L2: 151 34.7 65 L3: 144 33.1 62 Symmetra PX 160 kW Runtime: 1hr 1-min Capacity 10
ملخص المحتوى في الصفحة رقم 11
Overview: User Interface Menu tree Main Menu Power Dist UPS Switch Gear Environment Input UPS Power Total Loading Status Contacts Control Output Modular UPS Status Factory Relays Loading UPS Tests Alarm Relay Volt-Meter & Diags Map UPS Env Monitoring Subfeeds Configuration Card Alarms Help Log Admin System/ View All View New Network Alarms Log Items View by System ID View Entire Log Severity Manufacturer View by Type Clear Entire Log Data Firmware Updates Caution: Do not make changes to any s
ملخص المحتوى في الصفحة رقم 12
ملخص المحتوى في الصفحة رقم 13
Operation Operation Modes In an installation without a maintenance bypass panel, the UPS has four different operation modes. If the installation includes a PDU-XR or an external maintenance bypass panel, wrap-around maintenance bypass mode will also be available. Normal operation During normal operation, the UPS converts mains/utility power to conditioned power for the connected loads. Battery operation During battery operation, the UPS provides power to the connected loads from its external
ملخص المحتوى في الصفحة رقم 14
TRIP Operation Procedures Note: If the system does not contain a PDU-XR, the Q1, Q2, Q3, and Q5 switches are located on an optional external maintenance bypass panel. Refer to the documentation included with the maintenance bypass panel for additional information. Total Power Off procedure Warning: Before electrical installation begins, verify that the UPS is in the Total Power Off mode by following this procedure. UPS XR Battery enclosures / PDU-XR Set the SYSTEM ENABLE switch to the t
ملخص المحتوى في الصفحة رقم 15
Operation: Operation Procedures Set the upstream mains power to the OFF or LOCKED OUT position. If the UPS has a dual mains supply, set both supplies to the OFF or LOCKED OUT position. Electrical Hazard: Follow proper Lockout/Tagout procedures to remove access to the unit and physically label the unit as intentionally out of service. How to turn the load on/off using the display interface Press Press UPS Power Control UPS Alarms UPS Status Power Dist Log UPS Tests & Diags Switch Gear Ad
ملخص المحتوى في الصفحة رقم 16
Operation: Operation Procedures Set the Q2 switch on the PDU-XR to the OFF position. Turn the UPS off using the display. Press Press UPS Power Control UPS Alarms UPS Status Power Dist Log UPS Tests & Diags Switch Gear Admin UPS Configuration Environment Help Press Press Notify PowerChute? Turn UPS Off Cancel Reboot UPS Yes, Notify Servers UPS into Bypass No, Don’t Notify UPS to Sleep Turning UPS off, Turn UPS Off With please wait... Server Notification? >NO, ABORT >YES, Turn UPS
ملخص المحتوى في الصفحة رقم 17
Operation: Operation Procedures How to return to normal operation Set the DC DISCONNECT switch on all of the XR Battery enclosures and the PDU-XR to the ON position. Set the Q1 switch on the PDU-XR or external maintenance bypass panel to the ON position. Set the Q5 switch on the PDU-XR or external maintenance bypass panel to the ON position. Set the SYSTEM ENABLE switch on the UPS to the ON position. Note: Wait approximately 30 seconds for system to start. Using the display interfac
ملخص المحتوى في الصفحة رقم 18
Operation: Operation Procedures Press ESC to go back to the UPS Control screen and select UPS into Bypass. Note: The H2 LED next to the Q2 switch will illuminate, indicating that it is safe to operate the Q2 switch. Set the Q2 switch on the PDU-XR or external maintenance bypass panel to the ON position. Note: The H3 LED next to the Q3 switch will illuminate, indicating that it is safe to operate the Q3 switch. Set the Q3 switch on the PDU-XR or external maintenance bypass panel on the PDU
ملخص المحتوى في الصفحة رقم 19
Configuration System Settings How to change the date and time Use the UP and DOWN arrow keys to navigate through the menu screens. To change a setting, press ENTER and use the UP and DOWN arrow keys to change the selection. Press ENTER to save the changes. Press Press System/Network UPS Alarms System ID Power Dist Log Manufacturer Data Switch Gear Admin Firmware Update Environment Help Press Press System Password Date:>01Mar>2007 Date/Time Time:>02>24>00 Local Interface Network Addres
ملخص المحتوى في الصفحة رقم 20