ملخص المحتوى في الصفحة رقم 1
60kW InfraStruXure PDU
PD60F6FK1
PD60G6FK1
PD60L6FK1
PDRPPNX10
Operation and Configuration
208/400/600V Input
ملخص المحتوى في الصفحة رقم 2
ملخص المحتوى في الصفحة رقم 3
About This Manual Audience This manual is intended for end-users of a 60kW InfraStruXure PDU. It covers the operation and basic network configuration of the PDU, and includes basic InfraStruXure system operation. For additional information about the InfraStruXure system, see the InfraStruXure 60kW Installation and Start-Up Manual (990-1638B) which covers the installation and start-up of UPS power distribution to the rack and power distribution within the rack. Companion manuals For informatio
ملخص المحتوى في الصفحة رقم 4
ملخص المحتوى في الصفحة رقم 5
Contents Safety ......................................................................1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Safety symbols used in this manual . . . . . . . . . . . . . . . . . . . 1 Cross-reference symbols used in this manual . . . . . . . . . . . . . 1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ملخص المحتوى في الصفحة رقم 6
Volt-Meter Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Contacts Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Breakers Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Alarms Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 View Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Alarm/Event Log . . . . . . . . . . . . . . . . . . . . .
ملخص المحتوى في الصفحة رقم 7
Configuring the Network Management Interface . . . . . . . . . . . 37 Connect the InfraStruXure PDU to your network . . . . . . . . . 37 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 37 TCP/IP configuration methods . . . . . . . . . . . . . . . . . . . . . . 38 Device IP Configuration Wizard . . . . . . . . . . . . . . . . . . . . . 38 BOOTP & DHCP configuration . . . . . . . . . . . . . . . . . . . . . . 39 Local access to the control console . . . . . . . . . . .
ملخص المحتوى في الصفحة رقم 8
Product Information .............................................. 61 InfraStruXure Standard Warranty. . . . . . . . . . . . . . . . . . . . . . . 61 Life-Support Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 How to Obtain Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Appendix: Changes in This Manual........................ 65 vi 60 kW InfraStruXure PDU — Operation and Configuration
ملخص المحتوى في الصفحة رقم 9
Safety Overview Save these instructions This manual contains important instructions that must be followed during installation, operation, and maintenance of the InfraStruXure PDU. Safety symbols used in this manual Indicates an electrical hazard, which, if not avoided, could result in injury or death. Electrical Hazard Indicates a hazard, which, if not avoided, could result in personal injury or damage to product or other property. Warning Indicates a potential hazard which could result in da
ملخص المحتوى في الصفحة رقم 10
Warnings Receiving/moving Do not tilt the PDU greater than 45° from its vertical axis. Never lay the PDU on its side. Installation/Maintenance Only a certified electrician can: Connect the PDU to its power source Connect a switch to the EPO interface on the PDU Install a customer-specified, hard-wired power cable Only a certified electrician or an APC Field Service Engineer can perform maintenance of the PDU. When connecting the PDU to utility, a circuit breaker must be installed to prote
ملخص المحتوى في الصفحة رقم 11
Safety Total power off procedure 1. Open (turn OFF) the main circuit breaker of the power source feeding the PDU. 2. Open (turn OFF) the Main Input on the InfraStruXure PDU. 3. If applicable, open (turn OFF) the Main Output circuit breakers on the front of the PDU. For more information, see How to Ensure Total Power Off on page 33. Emergency Power Off (EPO) Hazardous voltage from the branch circuit must be isolated from the 24VAC, 24VDC, and contact closure. 24VAC and 24VDC are considered
ملخص المحتوى في الصفحة رقم 12
Safety EMI This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with this user manual, may cause harmful interference to radio communications. Operat
ملخص المحتوى في الصفحة رقم 13
Overview InfraStruXure PDU Front view The PDU Shielding Trough accommodates the power cables exiting the roof of the PDU, and separates power cables from data cables. The PDU power cables supply power to equipment racks; they are fed through knockouts on the top of the PDU. There are the following two options for PDU power cables: Multi-circuit power cables that terminate with an L21-20 outlet (shown). Single-circuit power cables that terminate with an L6-30 outle
ملخص المحتوى في الصفحة رقم 14
Overview Front view (interior) ! ! ! The 42-position circuit breaker panels provide 84 total pole positions. Each single pole provides power at 120 volts L-N or two single poles provide 208 volts L-L. The amperage each position provides depends on the size of the circuit breaker used. The document pocket provides storage of documents relating to the circuit breaker panels, such as the PDU Panel Board Schedules (provided). The Main Output breaker protects the distribution circuit b
ملخص المحتوى في الصفحة رقم 15
Overview Rear view of PDU with transformer (interior) The Main Input switch connects to your main power source. The switch accepts 208V, 480V, or 600V input and requires 3-wire input conductors. The PDU monitoring unit has several current and voltage monitoring boards that report to a central board assembly located in PDU monitoring unit. The PDU monitoring unit has one 10Base-T (Cat-5) connection to the Information Controller hub (or switch), four relay output connections, four
ملخص المحتوى في الصفحة رقم 16
Overview Rear view of PDU without transformer (interior) ! The Main Input circuit breaker connects to the main power source (UPS or utility). The breaker accepts 208V input and requires 4-wire input conductors. Note: This circuit breaker also serves as the Main Output (disconnect) circuit breaker. The PDU monitoring unit has several current and voltage monitoring boards that report to a central board assembly located in the PDU monitoring unit. The PDU monitoring unit has one 10
ملخص المحتوى في الصفحة رقم 17
Overview PDU monitoring unit This connection provides the input power for the PDU monitoring unit. The power is supplied by the monitoring unit circuit breaker on the front of the PDU. If the panel is on, and the monitoring unit circuit breaker is closed, the monitoring unit is powered. Connects to sensors monitoring values such as, voltage, current, and power. 885-2288 Digital input sensing for monitoring such as, circuit breaker status, transformer temperature, fans, etc. The D
ملخص المحتوى في الصفحة رقم 18
Overview User connection plate For a description and location of the user connection plate, see () on page 6. For clarity, the following illustration shows the user connection plate in greater detail. ! USER INTERFACE © 2001 APC MADE IN USA + EPO 24V 1 23 4 EPO Contact Inputs Contact Outputs AC/DC Contact ! Connect the InfraStruXure PDU to the network or the InfraStruXure Manager through the ethernet port. The user connection plate has four input contact connections for
ملخص المحتوى في الصفحة رقم 19
Multi-Branch Cordset Adapters APC offers three Multi-Branch Cordset Adapters. The adapters connect to a multi-branch power cord (whip) on the PDU and distribute three separate branches to Rack PDUs in your equipment racks. See the table below for compatible APC Rack PDUs. AP9882 L21-20P 5-20R AP9883 L21-20P L5-20R AP9884 L21-20P L6-20R 0 Compatible APC 120V PDUs SKU # Plug Outlets Manageable AP7530 L5-20P (24) NEMA 5-20R No AP9551 L5-20P (14) NEMA 5-15R No AP9563 L5-20P (10) NEMA 5-20R No A
ملخص المحتوى في الصفحة رقم 20
Overview Compatible APC 208V PDUs SKU # Plug Outlets Manageable AP7540 L6-20P (20) IEC 320 C13 No (4) IEC 320 C19 AP7840 L6-20P (20) IEC 320 C13 Yes (4) IEC 320 C19 AP7940 L6-20P (21) IEC 320 C13 Yes (3) IEC 320 C19 AP9510L620 L6-20P (1) NEMA L6-20R Yes SU045X163 L6-20P (1) NEMA L6-30R No 12 60 kW InfraStruXure PDU—Operation and Configuration