ملخص المحتوى في الصفحة رقم 1
Technical Instructions
Document No. 155-517P25
July 9, 2007
SQM5…
Reversing Actuators
ISO 9000 and 14000
REGISTERED FIRM
¤
Description
SQM5... reversing actuators are used for the positioning of flow control valves, butterfly
valves, dampers, or any application requiring rotary motion. The SQM5… actuators
accommodate control input signals of 4 to 20 mA, 0 to 135 Ω, 0 to 10 Vdc, 0 to 20 mA,
position proportional and floating control. The available output sig
ملخص المحتوى في الصفحة رقم 2
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 • Connections for both base and face mounting Features, Continued • Low hysteresis actuator and potentiometer gearing • Externally visible position indication • Selection of input and output signals • Zero and span adjustment • Field exchangeable circuit boards and potentiometers • Electronic damper linearization function • Split range and selectable parallel or master/slave operation • Adjustab
ملخص المحتوى في الصفحة رقم 3
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Table Of Contents Application Page 2 Product Numbers Product numbers for pre-assembled UL/CSA/CE-approved actuators, Table 1 Page 4 Product numbers for accessories, Table 2 Page 5 SQM5… Product Number Identification Legend Page 6 Installation and Operating Instructions Shaft Installation Page 7 Rotational Direction Verification Page 8 Actuator Mounting Page 8 Switch Adjustment
ملخص المحتوى في الصفحة رقم 4
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Table 1. Product Numbers for Pre-assembled Actuators. Product Numbers 1 3 Running Product Number Torque Input Control Signals 2 Time [lb-in] 90°@ 60 110 V 220 V 24 V Hzsec 90 8 ccw x x SQM50.261R1G3 90 8 cw x x SQM50.261R1G3R 90 8 ccw x SQM50.264R1A SQM50.264R2A 90 8 cw x SQM50.264R1A0R 90 8 ccw x SQM50.264R1A3 90 8 cw x x SQM50.264R1G3R 90 8 ccw x x SQM50.264R1G4 140 12 ccw x x SQM50.361R1G3 140
ملخص المحتوى في الصفحة رقم 5
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Table 2. Product Numbers for Accessories. Electronic Circuit Boards Shafts AGA58.1 10 mm round with key. Gear end only. AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxxAx AGA56.9A87 24 Vac (Z) board for SQM5x.xxxxxZx AGA58.2 12 mm round with key. Gear end only. AGA58.3 9 mm square. Dual-ended. AGA56.9A17 110 Vac (Z) board for SQM5x.xxxxxZx AGA58.4 3/8 inch square. Dual-ended. AGA56.9A27 220 Vac
ملخص المحتوى في الصفحة رقم 6
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Product Number Identification Legend For actuator identification only. To select product numbers for ordering, see Table 1. Figure 1. SQM5… Product Number Identification Legend. SQM5 0 .4 8 0 R 1 Z 3 R Actuator family Torque in-lb @ 60 (50) Hz. 0 90 for 8 (10) sec. running time 0 140 for 12 (15), 25 (30), 37 (45) sec. 3 200 for 25 (30) sec. 6 310 for 37 (45) sec. 6 400 for
ملخص المحتوى في الصفحة رقم 7
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Installation and SQM5… actuators are sometimes shipped without the shaft installed. To install the selected shaft: Operation Instructions 1. Loosen the two screws on the actuator cover corners. See Figure 2. 2. Lift the screws and raise the cover. See Figure 3. Shaft Installation Figure 3. Figure 2. 3. Each shaft is supplied with two washers and a “C” clip. See Figure 4. Using spreading
ملخص المحتوى في الصفحة رقم 8
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Actuator model numbers that end with “R” are factory configured for clockwise (cw), Rotational Direction minimum to maximum rotation when facing the gear end of the actuator, or Verification counterclockwise (ccw) rotation when facing the other end of the actuator. The gear end of the actuator is the side opposite of the visual position indicator. To field reverse the direction of rotation, see Se
ملخص المحتوى في الصفحة رقم 9
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Switch Adjustment, NOTE: If a potentiometer is installed, the adjustable range of the switches depends Continued on the range of the potentiometer. SQM5x.xxxxxAx actuators may be adjusted between 0 ° and 160 °. SQM5x.xxxxxx3 actuators have a 90 ° potentiometer and the switches must be adjusted only between 0 and 90 °. SQM5x.xxxxxx4 actuators have a 135 ° potentiometer and the switches must be
ملخص المحتوى في الصفحة رقم 10
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Wiring Connections NOTE: SQM5… actuators require a single source, single phase power supply. Wiring connections vary depending on which AGA56…. circuit board is installed. AGA56.1… circuit boards. Manual Operation See Figures 7 and 8. 1. Set the AUTO/MAN switch in the MAN position. 2. Connect ground to the screw located below the shaft release button. 3. Connect neutral to the double terminal blo
ملخص المحتوى في الصفحة رقم 11
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Wiring, Continued AZ L AZ L MAN. 0 AUTO. AGA56.1A97 Figure 8. AGA56.1A97 Terminal/Auto-Manual Board. Manual Operation AGA56.41/42/43… Circuit Boards. 1. Set the AUTO/MAN switch in the MAN position. See Figures 9 and 10. 2. Connect ground to the screw located below the shaft release button. 3. Connect neutral to terminal N. 4. Only terminal "L" must be powered to enable manual operation. The
ملخص المحتوى في الصفحة رقم 12
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Wiring, Continued A N Z 13 ZL LR L AGA56.4... Y+ AGA56.41... ("G" board 4...20 mA) Y- (+2 V) B U AGA56.42... 135 Ohm REG ("H" board OPE M W 0-135 Ohm) MAX MAX 0...2 V R Y MIN MIN MIN MAX Y M AGA56.43... 51 ("K" board 0...10 V) Y MIN MAX MAN AUTO shown in actuator switch auto position I Maximum/High fire II "Economy"/Fully closed III Minimum/Low fire IV...VI Auxilliary N 1 2 13 3 c 12 3 4 5 6 I II III I
ملخص المحتوى في الصفحة رقم 13
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 AGA56.9… Circuit Manual Operation Boards 1. Set the AUTO/MAN switch in the MAN position. See Figures 11 and 12. 2. Connect ground to the screw located below the shaft release button. 3. Connect neutral to terminal N. 4. Only terminal "L" must be powered to enable manual operation. The actuator can now be driven to the maximum (high fire) position (switch cam I) or the fully closed "economy pos
ملخص المحتوى في الصفحة رقم 14
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Wiring, Continued N A L Z ZL L1 P AGA56.9... POS LIN SHIFT ZF 4...20 mA MAX M 75% 50% POS 25% MIN (+2 V) B U4 MIN 25% 50%75% MAX Y0...3 0...3 Y0...3 Y 135 Ohm M W 0...2 V R Y0 POS M 1 REG 4...20 mA 2 OPE Y3 MAX MAX J1 M LIN MIN 0...10 V MIN Y1 MIN MAX Y0...3 M 0...20 mA MAX MIN Y2 51 U3 4...20 mA 1 U2 0...20 mA 2 U1 0...10 V MAN AUTO shown in J2 auto position actuator switch common M I Maximum/High fir
ملخص المحتوى في الصفحة رقم 15
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Modulation Adjustment The blue trim potentiometers allow the adjustment of the minimum (zero) and maximum (span) positions. See Figures 10 and 12. The factory setting of the MIN trim potentiometer is rotated fully counter clockwise. The factory setting of the MAX trim potentiometer is rotated fully clockwise. Zero Adjustment Set the OPE/MAX/MIN slide switch to MIN. The blue MIN trim potentiomete
ملخص المحتوى في الصفحة رقم 16
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 1. Lift the two screws on the cover corners and slide the cover end into the grooves Cover Installation at the gear end of the actuator. See Figure 14. 2. Press the cover into place and then press the screws inward and tighten. See Figure 15. Figure 14. Figure 15. Features of SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This SQM5x.xxxxxZx circuit board provi
ملخص المحتوى في الصفحة رقم 17
SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Electronic Linearization Butterfly valves have non-linear flow characteristics. Near the fully closed position, a Function small change in the valve’s position will produce a very large change in flow. Near the fully open position, a large position change will produce a relatively small change in flow. The linearization function is intended to minimize the initial steep flow curve characteristic
ملخص المحتوى في الصفحة رقم 18
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Features of SQM5x.xxxxxGx actuators contain the AGA56.41A… circuit board with terminals Y- and Y+ for 4 to 20 mA modulating input. SQM5x.xxxxxGx, SQM5x.xxxxxHx, SQM5x.xxxxxHx actuators contain the AGA56.42A… circuit board with terminals Y, M SQM5x.xxxxxKx and U for 0 to 135 Ω modulating input. Actuators SQM5x.xxxxxKx actuators contain the AGA56.43A… circuit board with terminals Y and M for 0 to
ملخص المحتوى في الصفحة رقم 19
max. min. max. min. max. min. max. min. BLUE BLACK BROWN BROWN BLACK BLUE BLUE BLACK BROWN BROWN BLACK BLUE BLUE BLACK BROWN BROWN BLACK BLUE SQM5… Reversing Actuators Technical Instructions Document No. 155-517P25 July 9, 2007 Reversing Rotational Direction, Continued POSITION POSITION INDICATION INDICATION POINTER POINTER POSITION INDICATION POINTER POSITION INDICATION POINTER Clockwise Counterclockwise Figure 17. Reversing Rotational Direction on the ASZ Potentiometer. G
ملخص المحتوى في الصفحة رقم 20
Technical Instructions SQM5… Reversing Actuators Document No. 155-517P25 July 9, 2007 Reversing Rotational 8. Firmly tighten the black potentiometer cam attachment screw while manually Direction, Continued holding the potentiometer position indication pointer in alignment. Check the alignment again. 9. Re-install the white actuator-indicating dial by gently pressing it onto the potentiometer cam attachment screw. Align scale position “0” on the actuator position indicating dial wit