ملخص المحتوى في الصفحة رقم 1
Product Data Document
420DS-7d / D301312X012
January 29, 2009 - Page 1
® ®
Bristol ControlWave ExpressPAC
SCADA RTU Package
Bristol® ControlWave® ExpressPAC, from Emerson
Process Management, is a highly integrated pre-
engineered package solution that combines the new
ControlWave Express SCADA RTU with a variety of
options commonly required in SCADA applications.
These include a compact Nema 4X rated enclosure,
power supply and solar panel options with battery
backup, operator display/keypa
ملخص المحتوى في الصفحة رقم 2
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 2 Bristol ControlWave ExpressPAC • 2 selectable Digital inputs/outputs tuning parameters, and outputs used in a measure- ment or control application. Status bits include • 2 selectable Digital inputs/counters the alarm state, alarm acknowledge, control, and manual (Auto/Man). Providing access to such vari- • 2 selectable Digital/Pulse inputs on CPU able information allows the user complete control • 3 optional Analog inpu
ملخص المحتوى في الصفحة رقم 3
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 3 Bristol ControlWave ExpressPAC • Adjustable timer turns off display when not in By adhering to such industry standards as Ethernet, use TCP/IP, Microsoft Windows®, COM/DCOM, FTP, OLE and ActiveX, ControlWave is able to achieve the highest degree of openness in control system Specifications – Display/Keypads architecture and bring the optimal process efficiency • Window size: 1.1” H x 3.1”W (2.8cm x 7.9cm) and productiv
ملخص المحتوى في الصفحة رقم 4
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 4 Bristol ControlWave ExpressPAC ACCOL III is designed to take full advantage of the • One RJ45 connector for interface to significant features offered by ControlWave. ControlWave LCD Display/Keypad Briefly, this library includes function blocks for: Power Input • Average, Compare, Totalize • 5.4 to 16 Vdc power input with 14 MHz CPU - Surge suppression 16 V transorb • Scheduling & Sequencing • 9.0 to 30.0 Vdc power input
ملخص المحتوى في الصفحة رقم 5
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 5 Bristol ControlWave ExpressPAC I/O RFI Susceptibility: Features • Convenient pluggable local 3V/m – 80 MHz to 1000Mhz (IEC 1000-4-3) • All configuration jumpers and switches Hazardous Area Approvals accessible without disassembly of circuit boards • Approved as non-incendive for operation in • Termination points for external loop power Class I, Division 2 supply • Class I, Division 1 approval pending for a subset of
ملخص المحتوى في الصفحة رقم 6
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 6 Bristol ControlWave ExpressPAC • Debounce: None Digital Outputs Accumulator: 16 bit • Number of points: 2 dedicated, 2 selectable DO (2 DI/DO) RTD Input • Output type: solid state open drain MOSFET • Input available on 14 MHz Ultra Low Power • Operating voltage range: 10 - 31Vdc CPU only • Maximum operating frequency: 20 Hz Specifications are for the interface, only, not including the RTD probe or wiring • Current
ملخص المحتوى في الصفحة رقم 7
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 7 Bristol ControlWave ExpressPAC 1-5 Vdc @ 5mA max., 11 to 30 Vdc external batteries are matched with solar panels as charging source sources. • D/A resolution: 12 bit Related to the power system, a charge regulator circuit and, in the 12 Vdc versions only, an auxiliary • Accuracy: output (AUX Output) is available in ControlWave 0.1% of span @ 25ºC for current output; ExpressPAC (except models with Ethernet). The AUX O
ملخص المحتوى في الصفحة رقم 8
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 8 Bristol ControlWave ExpressPAC Modem Specifications Radio Option The optional auto-dial / auto-answer modem pro- The ControlWave ExpressPAC is available with one vides a sleep mode that conserves power while optional FreeWave or MDS radio. allowing it to wake up when a call comes in. Since some users prefer to procure the radios sepa- • Function: Provides PSTN (Public Switched rately, Emerson offers “radio-ready” configu
ملخص المحتوى في الصفحة رقم 9
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 9 Bristol ControlWave ExpressPAC MDS entraNet 900 IP Radio Figures at 13.8 Vdc: • RS 232, Dial-line, cellular, radio, satellite, and Ethernet connections • Receive: 100 mA • Provides on-line download & signal variable • Transmit: 510 mA changes MDS iNet 900 Ethernet/IP Radio Figures at 13.8 • Allows network configuration through NetView Vdc: • PC and Network communication diagnostics • Receive: 203 mA • OPC Server for inter
ملخص المحتوى في الصفحة رقم 10
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 10 Bristol ControlWave ExpressPAC Local Configuration Wizard allows local commu- WebBSI - WebBSI is a powerful and flexible soft- nication with any attached ControlWave controller ware product bringing web technology to all of or RTU to download system flashware upgrades, Emerson’s Bristol automation and SCADA products. configure cold download parameters, and configure WebBSI includes a set of ActiveX Controls for read- IP
ملخص المحتوى في الصفحة رقم 11
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 11 Bristol ControlWave ExpressPAC • Configuration Info – works with a standard page presented as a text file in the PC. This functionality that displays and allows the user to change is extremely useful in providing an event trail during RTU Configuration information communication or PC downtime or other system problem. • Historical – Collect and view historical archive and audit files • Archive Collection – collection an
ملخص المحتوى في الصفحة رقم 12
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 12 Bristol ControlWave ExpressPAC ControlWave Open Network Connectivity While BSAP is an open protocol, the added func- tionality of the messages provide much more capa- By embracing the open system network technolo- bility than is found in other networks. gies available through TCP/IP, Ethernet, OPC, and • Global time-synchronization Microsoft DNA, as well as pseudo standards such as Modbus and Open Modbus, ControlWave ca
ملخص المحتوى في الصفحة رقم 13
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 13 Bristol ControlWave ExpressPAC Multi-user Security Access further ensure that the data is always current and historically accurate, the historical data is stored Security is an essential element of any open in non-volatile flash memory within ControlWave. system, particularly those with Internet access. Historical data is even maintained during and after ControlWave employs a User Name/Password ac- program downloading.
ملخص المحتوى في الصفحة رقم 14
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 14 Bristol ControlWave ExpressPAC Model Specifications Model Number: CWEPAC - A - B - C D - E - F - G - H J - K - L M N DESCRIPTION CODE A Integral Enclosure and LCD/Keypad A 7½” x 11¾” Lexan with LCD display only, no Keypad 1 10 7½” x 11¾” Lexan, LCD, 2 Keys 2 7½” x 11¾” Lexan, LCD, 25 Keys 3 B Power System B None - External Power Source is Necessary 1 7.2 V Lithium Battery, Single 2 7.2 V Lit
ملخص المحتوى في الصفحة رقم 15
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 15 Bristol ControlWave ExpressPAC Model Specifications, continued Model Number: CWEPAC - A - B - C D - E - F - G - H J - K - L M N DESCRIPTION CODE F Mounting F 50 Pole mount (pipe clamp and brackets) 1 Panel mount (with 4 fastening ears) 2 G H Application Program G H 60 None 00 01 J Hazardous Area Certification J 70 None 0 Class I, Division 2 Non-incendive (UL/CUL - NI) 1 Remote Automation Solutions Website: www.
ملخص المحتوى في الصفحة رقم 16
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 16 Bristol ControlWave ExpressPAC Model Specifications, continued Model Number: CWEPAC - A - B - C D - E - F - G - H J - K - L M N DESCRIPTION CODE K Radio Cable/Mounting Hardware and Polyphaser Option XCWMPOLY K No Radio 0 80 Without Polyphaser Don’t forget to specify a “1” or “2” here 1 With Polyphaser if a radio is selected in ‘LMN’ below! 2 L M N Radio or Modem Option XCWMGRADIO L M N None 000 90 Dial-li
ملخص المحتوى في الصفحة رقم 17
Product Data Document 420DS-7d / D301312X012 ® January 29, 2009 - Page 17 Bristol ControlWave ExpressPAC Remote Automation Solutions Website: www.EmersonProcess.com/Remote